Chapter 4 Testing 55
NetSure 801 CA7 Power Supply System (New Skelecton) User Manual
Charge
Charge>
Battery Test
Battery Test>
Yes
Constant Curr Test:
Temp Comp
Temp Comp>
LargeDU>
LargeDU
Large DUBatt1
2000
2000
Large DUBatt2
70%
EndTestCapacity:
180min
End Test Time:
No
TempComp Sensor:
Batt Settings
None
TempComp Center:
25deg.C
72mV/deg.C
Temp Comp Coeff:
45.2V
End Test Voltage:
Auto EQ
0.30C10
Over Curr Lmt:
0.10C10
Batt Curr Limit:
56.4V
EQ Voltage:
53.5V
Float Voltage:
Figure 4-7 Setting battery charge parameters
Charge
Charge>
Battery Test
Battery Test>
Yes
Constant Curr Test:
Temp Comp
Temp Comp>
LargeDU>
LargeDU
Large DUBatt1
2000
2000
Large DUBatt2
70%
EndTestCapacity:
180min
End Test Time:
No
TempComp Sensor:
Batt Settings
None
TempComp Center:
25deg.C
72mV/deg.C
Temp Comp Coeff:
45.2V
End Test Voltage:
Auto EQ
0.30C10
Over Curr Lmt:
0.10C10
Batt Curr Limit:
56.4V
EQ Voltage:
53.5V
Float Voltage:
Figure 4-8 Battery current coefficient
Back to
‘Batt Settings’ screen, enter ‘Temp Comp’ screen, set the ‘Temp Comp Coeff’ according to battery factory
requirement. The default value is 72mV/°C (If no temperature sensor is configured, ignore this item), and set the
‘TempComp Sensor’ to ‘Ldu1 Temp1’, as shown in Figure 4-9. (If no temperature sensor is configured or the
temperature compensation function needs to be canceled, then set the
‘TempComp Sensor’ to ‘None’). Meanwhile,
set
‘DC Settings’
’DC Distrib 1
’Temp Number’ to 1 ~ 3 ( if no temperature sensor is configured or the temperature
compensation function needs to be canceled, then set the
‘Temp Number’ to ‘0’), as shown in Figure 4-10.
Charge
Charge>
Battery Test
Battery Test>
Yes
Constant Curr Test:
Temp Comp
Temp Comp>
LargeDU>
LargeDU
Large DUBatt1
2000
2000
Large DUBatt2
70%
180min
End Test Time:
No
TempComp Sensor:
Batt Settings
None
TempComp Center:
25deg.C
72mV/deg.C
Temp Comp Coeff:
45.2V
End Test Voltage:
Auto EQ
0.30C10
Over Curr Lmt:
0.10C10
Batt Curr Limit:
56.4V
EQ Voltage:
53.5V
Float Voltage:
Figure 4-9 Setting Temp Comp parameter
DC Settings
DC DistGroup>
Over Voltage:
58.5V
45.0V
Under Voltage:
Num of Battery:
2
Temp Number:
0
Branch CurrCoeff:
Curr Output Num:
Load Measure Ty:
Hall
Hall Coefficient:
32
3000
500
DC DistGroup
DC Distrib1>
DC Distrib1
Figure 4-10 Setting Temp Number
Note