Chapter 1 Introduction 3
NetSure 801 Series Power Supply System User Manual
Parameter
Description
Mechanical
Dimensions
mm (H × W
× D)
Recitifier cabinet
2000mm × 600mm × 600mm
Controller(M831D)
42mm × 86.60mm × 211.5mm
Recitifier (R48-5800A
、
R48-5800e)
88mm × 244mm × 372mm
Weight (kg)
Recitifier cabinet (not include
the rectifier)
Rack1000-7
≤ 140
;
Rack2000-7
≤ 180
Controller(M831D)
≤ 2
Recitifier (R48-5800A
、
R48-5800e)
≤ 8
The technical parameter of the AC distribution cabinet is given in Table 1-2.
Table 1-2 Technical parameter of AC distribution cabinet
Parameter
Description
Environmental
Operating temperature
-5°C ~ 40°C;
Storage temperature
-45°C ~ 70°C
Relative humidity
5%RH ~ 95%RH
Altitude
≤ 2,000m (derating is necessary above 2,000m)
Others
No conductive dust or erosive gases. No possibility of explosion
AC input
Input system
TN-C, TN-S, TN-C-S, TT, 3- phase 4-wire and 3- phase 5-wire network
forms
Rated line voltage
380Vac
Voltage range
260Vac ~ 530Vac (errors: 5Vac)
Frequency
45Hz ~ 65Hz
45Hz ~ 55Hz (Configuring PD380/630AFA-7-Y1)
AC output
Distribution parameter
PD380/400AFH-7-Y2:
6 route 3- phase input, 6 route single phase output
,
Output total capacity
does not exceed 400A:
160A/3P × 4, 63A/3P × 1, 32A/3P × 1, 32A/1P × 3, 20A/1P × 3
PD380/630AFH-7-Y3:
8 route 3- phase input, 6 route single phase output
,
Output total capacity
does not exceed 630A:
160A/3P × 6, 63A/3P × 1, 32A/3P × 1, 32A/1P × 3, 20A/1P × 3
PD380/630AFH-7/YF: Configured according to customer requirement (IF
the input switch using MCB, shall not exceed the total capacity of the
Cabinet input of MCB 80%)
AC output
Distribution parameter
PD380/630AFA-7/Y4:
8 route 3- phase input, 6 route single phase output
,
Output total capacity
does not exceed 600A:
160A/3P × 6, 63A/3P × 1, 32A/3P × 1, 32A/1P × 3, 20A/1P × 3
Mechanical
Dimensions mm (W × D × H)
2000mm × 800mm × 600mm
Weight (kg)
PD380/400AFH-7-Y2, PD380/630AFH-7-Y3
≤ 240,
PD380/630AFA-7-Y4
≤ 250, PD380/630AFH-7/YF ≤ 270
The technical parameter of the DC distribution cabinet is given in Table 1-3.
Table 1-3 Technical parameter of DC distribution cabinet
Parameter
Description
Environmental
Operating temperature
-5°C ~ 40°C;
Storage temperature
-45°C ~ 70°C
Relative humidity
5%RH ~ 95%RH
Altitude
≤ 2,000m (derating is necessary above 2,000m)
Others
No conductive dust or erosive gases. No possibility of explosion
DC input
Rated voltage
48Vac
Voltage range
42Vac ~ 57.6Vac (errors: 0.3Vac)
Rated input current
PD48/1600DF-7-Y3: 1600A; PD48/1600DF-7-Y4: 1600A;
PD48/2500DF-7-Y3: 2500A; PD48/2500DF-7-Y4: 2500A
DC output
Load current
PD48/1600DF-7-Y3:
≤ 1200A; PD48/1600DF-7-Y4: ≤ 1200A;
PD48/2500DF-7-Y3:
≤ 2000A; PD48/2500DF-7-Y4: ≤ 2000A