NetSure 7100 Series -48V DC Power System Installation Manual (IM582127000)
|
Rev. BB
182
Battery Connections to Bay-to-Bay Rectifier Busbars (582127000 List 1 with List 2 / List 3) (for system
mounted in a relay rack)
DANGER!
Adhere to the “Important Safety Instructions” presented at the front of this document.
IF THE SYSTEM DOES NOT CONTAIN A BATTERY SHUNT OR BATTERY DISCONNECT CONTACTOR,
battery may be connected to the 582127000 List 2 and List 3 bay-to-bay rectifier busbars located on the rear of
the distribution cabinets, as detailed in
, depending on site requirements.
Figure 107:
Battery Connections to Bay-to-Bay Rectifier Busbars (for system mounted in a relay rack)
RECTIFIER AND RECTIFIER RETURN CONNECTIONS
(CAN ONLY BE USED FOR BATTERY CONNECTIONS
IF THE SYSTEM DOES NOT CONTAIN A BATTERY
SHUNT OR BATTERY DISCONNECT CONTACTOR)
3/8-16 Captive Nuts on 1” Centers
(Customer must supply additional hardware.)
Maximum Lug Width: 1.88 inches.
(See Detail A)
Rear
GND RETURN
Rectifier (Return Side) Busbar
-48V Supply
Rectifier (Load Side) Busbar
Rear busbar cover shields
not shown in illustration.
Detail A
Notes:
1. All dimensions are in inches.