Vertiv
|
NetSure 502NGFB Installation Manual (Section 6009)
|
Rev. Z
49
Optional External Battery Disconnect Unit
for battery and alarm connection details to the optional External Battery Disconnect Unit
and torque information. Also provided are alarm connection details to battery disconnect circuit breakers
located on the optional battery trays and battery cabinets.
Figure 22:
External Interface Connections (cont’d on next page)
Yellow Alarm Lead
(P/N 535294)
(factory wired to
circuit breaker
alarm terminal)
Connect to shelf
per table below.
Remove quick
connect terminal
first.
Torque to 84 in-lbs
using supplied hardware
To
Power
System
To
Battery
Procedure
1. Connect YELLOW lead exiting top of
Battery Disconnect Unit per table below.
Remove quick connect terminal first.
The YELLOW lead is factory connected
to circuit breaker “C (Common)” alarm
terminal in the Battery Disconnect Unit.
2. There is NO connection to the circuit
breaker “NO (Normally Open)”
alarm terminal.
3. Connect loose end of Jumper factory
connected to bottom terminal on
circuit breaker to circuit breaker
“NC (Normally Closed)” alarm
terminal.
Alarm Wiring to a Single
External Battery Disconnect Unit
541311 Alarm Cable
on shelf
NO
YES
BREAKER ALARM CONNECTION
CONNECT YELLOW WIRE TO:
Pin 3 of J3 on Customer Interface board
(negative side of Digital Input 2)
O-R Lead of 541311
Splice and heat shrink tubing included with 541311
Содержание NetSure 502NGFB Series
Страница 10: ...Vertiv NetSure 502NGFB Installation Manual Section 6009 Rev Z 10 This page is intentionally blank ...
Страница 37: ...Vertiv NetSure 502NGFB Installation Manual Section 6009 Rev Z 37 Figure 14 Controller RJ 45 Ethernet Port ...
Страница 45: ...Vertiv NetSure 502NGFB Installation Manual Section 6009 Rev Z 45 Figure 20 Battery Connections ...
Страница 85: ...Vertiv NetSure 502NGFB Installation Manual Section 6009 Rev Z 85 This page is intentionally blank ...
Страница 86: ...Vertiv com Vertiv Headquarters 1050 Dearborn Drive Columbus OH 43085 USA Section 6009 RZ 2020 ...