NetSure™ Site Monitoring Unit Installation & User Manual (UM10010507)
|
Rev. A
15
NCU CAN Bus Connections
Procedure (Connecting First SM-DU+ Assembly to NCU)
1.
Connect the SM-DU+ assembly into the NCU CAN Bus. Connect CAN_H to CAN_H. Connect CAN_L to
CAN_L. Refer to the system documentation for NCU CAN port description and location. Cable P/N
562868 provided. Refer to
for cable information. Refer to
Table 3:
CAN Bus Cable P/N 562868
Connector
Pin No.
Color
Signal Symbol
RJ-45
1
W/O
CAN_L
2
O
CAN_H
Procedure (Connecting Multiple SM-DU+ Assemblies Together)
NOTE!
The NCU can communicate with up to eight (8) SM-DU+ assemblies. Set each SM-DU+
assembly to a unique address number.
1.
To connect multiple SM-DU+ assemblies together, for all assemblies connect the CAN_H terminals
together and connect the CAN_L terminals together (CAN_H to CAN_H, CAN_L to CAN_L). See
2.
Connect a termination resistor such as P/N 561768 to the last SM-DU+ assembly in the NCU CAN bus.
Connect to CAN_H and CAN_L terminals along with the CAN_H and CAN_L leads factory connected to
the terminal block. See