10.2 Fluid and Piping Maintenance
Maintaining the system fluid quality is required throughout the life of the system. Fluid and piping system maintenance
schedules must be established and performed. A coolant fluid maintenance program must be established that will evaluate
fluid chemistry and apply necessary treatment. The complexity of water condition problems and the variations of required
treatment programs make it extremely important to obtain the advice of a competent and experienced water treatment
specialist and follow a regularly scheduled coolant fluid system maintenance program.
Perform periodic inspections of the heat exchanger and coolant fluid piping system for leaks and visible damage.
10.3 Spare Parts
Only original spare parts made by Vertiv must be used. Using third-party material will invalidate the warranty. When
seeking technical assistance, always refer to the component list supplied with the equipment, and specify the model
number, serial number and, if available, the part number.
NOTE: When replacing a faulty component, follow the relevant manufacturer instructions.
NOTE: When the spare parts must be brazed, be careful not to damage the internal parts (gaskets, seals,
O-rings, etc.).
10.4 Maintenance Schedule
Conduct monthly, quarterly, biannual, and annual checks according to the following guidelines.
All tasks and time periods listed here are the manufacturers’ regulations and must be documented in an inspection report.
Component
Maintenance Period
Monthly By
User
Every
3 Months
Every
6 Months
Annually
General
Check unit display for clogged-filter
warning.
X
Check for irregular noise from unit
fans.
X
Check and clean strainer.
X
Blowers
Verify impellers move freely.
X
Check bearings.
X
Check motor mounts for tightness.
X
Check fan safety switch.
X
Electrical/Electronics
Check condition of contacts.
X
Check electrical connections.
X
Check operation of controller.
X
Check unit operation sequence.
X
Table 10.1 Maintenance Schedule
Vertiv | XDU™ Liquid to Air Heat Exchanger for Chip Cooling
42
Содержание Liebert XDU 060
Страница 1: ...Liebert XDU Liquid to Air Heat Exchanger for Chip Cooling Installer User Guide 600 mm Wide ...
Страница 10: ...Vertiv XDU Liquid to Air Heat Exchanger for Chip Cooling 6 This page intentionally left blank ...
Страница 14: ...Vertiv XDU Liquid to Air Heat Exchanger for Chip Cooling 10 This page intentionally left blank ...
Страница 18: ...Vertiv XDU Liquid to Air Heat Exchanger for Chip Cooling 14 This page intentionally left blank ...
Страница 38: ...Vertiv XDU Liquid to Air Heat Exchanger for Chip Cooling 34 ...
Страница 42: ...Vertiv XDU Liquid to Air Heat Exchanger for Chip Cooling 38 This page intentionally left blank ...
Страница 52: ...Vertiv XDU Liquid to Air Heat Exchanger for Chip Cooling 48 This page intentionally left blank ...
Страница 56: ...Vertiv XDU Liquid to Air Heat Exchanger for Chip Cooling 52 This page intentionally left blank ...
Страница 58: ...Vertiv XDU Liquid to Air Heat Exchanger for Chip Cooling 54 This page intentionally left blank ...
Страница 59: ...Appendix B Performance Curves Figure B 1 Liebert XDU Performance Test Results 45 C 113 F LFT 55 ...
Страница 62: ...Vertiv XDU Liquid to Air Heat Exchanger for Chip Cooling 58 This page intentionally left blank ...
Страница 64: ...Vertiv XDU Liquid to Air Heat Exchanger for Chip Cooling 60 This page intentionally left blank ...
Страница 74: ...Vertiv XDU Liquid to Air Heat Exchanger for Chip Cooling ...