24
thickness selection, otherwise it may cause system leakage or pipe burst.
Improper selection of the piping material may cause system leakage or piping burst, contact Vertiv
local representative for more details.
2.8.3. Branch Manifold
As shown in
, when connecting the main piping and the branch piping, a branch manifold
installation is required. If the branch manifold is not available then a T-shaped 3-way connector with suitable pipe diameter
can be used.
Before connecting the branch manifold, cut the branch manifold according to the pipe diameter of the branch pipe.
Figure 2-15 Branch Manifold of Suction Pipe
Figure 2-16 Branch Manifold of Liquid Return Pipe
After selecting the appropriate pipe diameter, use a micro cutter to break the piping according to the actual piping on site,
refer
for better understanding.
ITEMS
DESCRIPTION
1
Interrupt according to the actual situation on site
Figure 2-17 Branch Manifold Processing
Note: Remove the residual burrs after cutting the piping to avoid choking in the piping.