Mechanical Installation
15
ITEMS
DESCRIPTION
ITEMS DESCRIPTION
1
Condenser
3
Floor
2
Slope
4
Oil return bend
Figure 2-8 Installation of Terminal or Outdoor Unit Lower than Liebert XDC
Note: Refer to the installation diagram to ensure that the relevant pipeline is at least 1/100 inclination.
Note: Refer to the installation diagram. When the outdoor unit is higher than Liebert XDC, or the terminal is lower than
Liebert XDC, pay attention to install an oil trap on the air pipe.
2.7. Installation of the Unit
2.7.1. Mechanical Parameters
The Vertiv™ Liebert® XDC unit dimensions and mechanical parameters are shown in
.
Figure 2-9 Dimension of Liebert XDC