XDC160 Water Floor Stand - 60Hz
189192G5
189192G3
Entering Fluid Temp °F (°C)
65 (18)
70 (21)
75 (24)
85 (29)
95 (35)
Performance Data
Cooling capacity, tons (kW)
46.1(162.3)
46.1(162.3)
46.1(162.3)
46.1(162.3)
44.5(156.5)
Flow, GPM
50
58
70
110
142
Pressure Drop, psi (Ft Water)
2.7 (6.2)
4.9 (11.3)
5.4 (12.5)
20.7 (47.8)
27.3 (63.1)
Heat Rejection Equipment
Water regulating valve size
1"
1"
1"
1"
1"
Piping Connections
Water / glycol supply and return lines
2-1/8"
2-1/8"
2-1/8"
2-1/8"
2-1/8"
Table 9.14 Floor stand specifications—water-cooled Liebert XDC
XDC160 Glycol Floor Stand - 60Hz - 40% PG
189192G3
Outside Ambient °F (°C)
95 (35)
100 (38)
105 (41)
Max Entering Fluid Temp °F (°C)
110 (43)
110 (43)
110 (43)
Performance Data
Cooling capacity, tons (kW)
42.5 (149.4)
Total Heat Rejection, (kW)
192.6
Flow, GPM
206
Pressure Drop, psi (ft water)
37.2 (85.9)
Heat Rejection Equipment
Drycooler
DDNT 940A
2 x DDNT 880A*
Drycooler Pressure Drop, psi (ft water)
6.7 (15.8)
2.9 (6.6)
Glycol pump package - 10hp
460V - D10ANTS1317; 208V - D10YNTS1317
Pump Control Package - 208V
RP020HY04S0758
Pump Control Package - 460V
RP020HA08S0758
Pump Total Head @ 206 GPM, ft water
145
Water regulating valve size
1-1/4"
Piping Connections
Water / glycol supply and return lines
2-5/8"
*When multiple drycoolers are used, ensure flow is balanced.
Table 9.15 Floor stand specifications—Liebert XDC with 40% propylene glycol
Vertiv
| Liebert® Xtreme Density™ System Design Manual |
195
Содержание Liebert XD Series
Страница 1: ...Liebert Xtreme Density System Design Manual...
Страница 18: ...Vertiv Liebert Xtreme Density System Design Manual 18 This page intentionally left blank...
Страница 20: ...Vertiv Liebert Xtreme Density System Design Manual 20 This page intentionally left blank...
Страница 45: ...Figure 3 22 Liebert XD return header orientation Vertiv Liebert Xtreme Density System Design Manual 45...
Страница 66: ...Figure 4 2 Overall dimensions Vertiv Liebert Xtreme Density System Design Manual 66...
Страница 76: ...Figure 4 12 Liebert XDO internal mounting location Vertiv Liebert Xtreme Density System Design Manual 76...
Страница 88: ...Figure 4 21 Liebert XDV dimensions Vertiv Liebert Xtreme Density System Design Manual 88...
Страница 90: ...Figure 4 23 Suspending single Liebert XDV from Unistruts Vertiv Liebert Xtreme Density System Design Manual 90...
Страница 103: ...Figure 5 4 Piping locations floor stand and valve assembly Vertiv Liebert Xtreme Density System Design Manual 103...
Страница 112: ...Figure 5 16 Front view of Liebert XDP and electrical enclosure Vertiv Liebert Xtreme Density System Design Manual 112...
Страница 115: ...Figure 5 19 Liebert XDP high voltage connections 60Hz Vertiv Liebert Xtreme Density System Design Manual 115...
Страница 116: ...Figure 5 20 Liebert XDP high voltage connections 50Hz Vertiv Liebert Xtreme Density System Design Manual 116...
Страница 120: ...Figure 6 2 Condenser planning dimensional data Six fan units Vertiv Liebert Xtreme Density System Design Manual 120...
Страница 121: ...Figure 6 3 Typical condenser footprint dimensions Vertiv Liebert Xtreme Density System Design Manual 121...
Страница 138: ...Figure 6 13 Drycooler planning dimensional data Eight fan units Vertiv Liebert Xtreme Density System Design Manual 138...
Страница 152: ...Vertiv Liebert Xtreme Density System Design Manual 152 This page intentionally left blank...
Страница 166: ...Figure 7 7 Modules on a single chain Vertiv Liebert Xtreme Density System Design Manual 166...
Страница 167: ...Figure 7 8 Modules on two chains Vertiv Liebert Xtreme Density System Design Manual 167...
Страница 170: ...Figure 7 11 CAN Isolator location within the Liebert XDP XDC Vertiv Liebert Xtreme Density System Design Manual 170...
Страница 182: ...Vertiv Liebert Xtreme Density System Design Manual 182 This page intentionally left blank...
Страница 198: ...Figure 9 7 Liebert XDP model number nomenclature Vertiv Liebert Xtreme Density System Design Manual 198...
Страница 199: ......