TEMPERATURE/HUMIDITY TRANSMITTER - WALL (4-20 

M

A)

Product Specification/Installation Guide

590-1616-501A\SL-31080_REV2_11-17

      

3

You will measure the humidity 

output by placing an ammeter in 

series with the controller input. The 

controller input is connected to the 

terminal marked “Ch1 or Ch2” on the 

humidity board.

1.  Verify the unit is terminated 

properly using Figure 4 shown 

below, and set your meter to the 

“Volts” setting.

2.  Verify you have 24 VDC 

supplied to the unit by 

measuring between the “V+” 

and “GND” terminals at the 

sensor, as shown below in 

Figure 3.

3.  Set your meter to “Amps” and 

measure the output between 

“Ch1 or Ch2” and the controller 

input as shown below in Figure 3.

4.  Use the following formula to 

determine what humidity the 

sensor is reading: 

(mA - 4) / 0.16 = %RH 

where mA is the current reading 

from the ammeter (in mA)

TROUBLESHOOTING 

- Humidity Signal Verification

TROUBLESHOOTING GUIDE

PROBLEMS

POSSIBLE SOLUTIONS

Unit will not operate

• Check +24 VDC power supply at controller.
• Disconnect the sensor and check power wires for +24 VDC.

Humidity reading is maximum 20 mA or 
100%

• Make sure the sensor is wired properly.

Humidity reading is minimum 20 mA or 
0%

• Verify that the humidity sensor is wired properly.

Humidity reading in software appears to 
be off more than specified

• Check all software parameters.
• If available, check the sensor against a calibrated control such as a hygrometer.
• Determine if the sensor is exposed to an external source more than room.

Temperature sensor in front end software 
is reading high

• Make sure wiring is correct.
• Disconnect wires and measure with a multimeter.

The following table lists common problems and possible solutions. For more information, consult your local
dealer, Liebert representative or the Liebert Worldwide Support Group.

Example:

If the current reading is       

16 mA, then:
%RH   =   (16 - 4) / 0.16
 

=   12 / 0.16

 

=   75%

Figure 1 

- Supply Voltage and 4-20mA Verification

Figure 2 

- 4-20mA Output Connection

ORDERING INFORMATION

PART #

DESCRIPTION

THW420

Combination Temperature/Humidity Transmitter Wall 4-20 mA @ 45°F to 96°F
and 0 to 100% RH