Figure 4.2 Removing the battery box from 1U units to replace batteries
ITEM
DESCRIPTION
1
Remove front panel.
2
Disconnect red then black wire from battery terminals.
3
Remove screws and metal battery cover.
4
Connect black then red wire to battery terminals.
5
Slide the replacement battery kit into the UPS. Replace the metal plate and secure with the two screws.
6
Reconnect the battery connector.
7
Snap the front panel back on.
To replace the batteries on MT models:
1.
Place the unit on its left side and remove the 6 screws and the metal battery cover plate.
2.
Slide out the existing battery kit and disconnect the two halves of the battery connector.
3.
Orient the connector and the new battery in the same way as the original battery, connect the two halves of the
battery connector, and slide into UPS.
4. Replace the metal plate and secure with the 6 screws.
5.
Press and hold the power button for 3 seconds to initiate the Battery-Self Check mode clearing any previous
battery fault warning.
6. Properly dispose of the old batteries at an appropriate recycling facility or return them to Vertiv™ in the
packing material from the new batteries.
4 Maintenance and Battery Replacement
35
Содержание LIEBERT PSI5 MINI-TOWER PSI5-1500MT120
Страница 1: ...Liebert PSI5 120V Input 120V Output 208V Input 208V Output Installer User Guide...
Страница 6: ...Vertiv Liebert PSI5 Installer User Guide 2 This page intentionally left blank...
Страница 18: ...Vertiv Liebert PSI5 Installer User Guide 14 This page intentionally left blank...
Страница 36: ...Vertiv Liebert PSI5 Installer User Guide 32 This page intentionally left blank...
Страница 57: ...Vertiv Liebert PSI5 Installer User Guide...