Figure 18 Optional Input Contact Isolator Board
1 2 3
6 7 8 9
4
10
5
11 12 13 14 15 16
J51
No Customer Connection
Table 11
Input Contact Isolator
Board control wiring
connections
Input
Contact
Pin No.
1
1
2
2
3
4
3
5
6
4
7
8
5
9
10
6
11
12
7
13
14
8
15
1.
Customer control wiring connection points are terminals 1 through 16
(see
2.
Customer provided normally open dry contacts for user alarm
messages.
3.
All control wiring (by others) must be run separate from power wiring.
Control wiring runs should not be combined in the same conduit.
4.
Signal voltage: 100mA @ 12VDC.
5.
Maximum cable length 500 ft. (152m) with #16AWG and flexible
Содержание Liebert NXL 500kVA