Vertiv | Liebert
®
NXL
™
500-750kVA UPS Installation Manual |
29
•
Assignment—Custom, Pre-assigned (default: “Input Contact” XY)
•
Delay, sec—0 to 99.9 (default: 0)
•
Message—Custom: 0-19 characters
3.
To assign labels for each channel:
a.
Press Pre-assigned for default labels on Channels 1-6 (See
)
b.
For Custom labels
1.
Press Custom to unique labels.
2.
Click on Input Contact XX button. A keyboard is displayed to allow naming alarms.
3.
Enter the name of the alarm set for that input. For example, a fan problem could be indicated by naming
the button FAN.
4.
Press OK on the keyboard to keep your label.
4.
Press DELAY.
a. A keypad is displayed prompting you for a delay time, in seconds, for a condition to exist
before the alarm is triggered.
b. Enter the delay value. The range for the values are from 0 (zero) to 99.9 seconds.
c. Press OK on the keypad to keep your setting. The value you entered is displayed in the field
adjacent to the corresponding input contact.
5.
6.
Press SAVE after you have configured all input contacts.
Be sure to press Save even if you have accessed this dialog only to change a setting.
7.
This information is not saved if control power is removed.
Table 10
Input Contact Isolator Board pre-assigned values
Channel
Number
ICI #1
Pre-Assigned Label
ICI #2
Pre-Assigned Label
1
Reduced Rect ILimit
Stop Battery Charge
2
Reduced Batt ILimit
Stop Battery Charge
3
Stop Battery Charge
Stop Battery Charge
4
Inhibit Rect Restrt
Stop Battery Charge
5
Inhibit Byp Restrt
Stop Battery Charge
6
Inhibit Inv Restrt
Stop Battery Charge
7
Input Trap Filter
Disconnect
Inhibit IP Standby
8
Suspend ECO Mode
—