Vertiv LIEBERT MPX PEM Скачать руководство пользователя страница 1

LIEBERT® MPX™ PEM

Quick Installation Guide

SL-20821_REV7 

590-1624-501B

1

WARNING

: Before assembling and 

installing a Liebert® MPX™, read 

and understand all warnings and 

cautions in the Liebert® MPX™ 

Rack Power Distribution Unit User 

Manual which can be downloaded 

at www.VertivCo.com.  

 

Vertiv strongly recommends that 

the MPX power entry module 

(PEM) be installed by an individual 

who is properly trained and 

qualified to perform electrical work. 

 

The MPX rack PDU contains high 

voltage that can cause serious 

personal injury or death. Install the 

unit in a restricted-access location.  

 

Connecting input power before the 

MPX PEM is installed can cause arc 

flash and can result in death. Do 

not connect input power to the 

MPX PEM until the MPX rack PDU 

is fully assembled.  

Do not connect more than one 

MPX PEM to an MPX power rail 

chassis (PRC). Installing more than 

one MPX PEM will result in serious 

injury or equipment damage.

To attach an MPX™ PEM to an 

MPX™ PRC:

1.  Preparing for installation

Ensure the module’s circuit breaker 
is in the off/open position and the 
screw latches at each end of the 
MPX PEM are positioned to fit into 
the MPX PRC slot. 

2.  Aligning the MPX PEM power 

blades

Position the MPX PEM so the power 
blades align with the power bus on 
the MPX PRC. 

3.  Positioning and connecting 

the module to the MPX PRC

Hold the MPX PEM at an angle 
against the MPX PRC end cap and  

press down so that the MPX PEM 
power blades engage firmly into the 
MPX PRC power bus.

4.  Securing the module to the 

MPX PRC

Use the provided tamper-resistant 
Torx™ (TR20) screwdriver bit  to 
press each screw latch downward. 
Turn the screw latch 90 degrees 
(one-quarter turn) to seat the 
locking tab. Turn the screw latch an 
additional 180 degrees (one-half 
turn) until it locks.

WARNING: 

Do not use power 

tools or pneumatic equipment 

to secure the screw latch.
Do not turn the screw latch 

more than 270 degrees (a 

three-quarter turn). 

NOTE

: If using a torque-

limiting screwdriver, carefully 

press the screw downward 

first before turning. To prevent 

MPX™ PEM  

Bottom view

MPX™ PEM Configuration

End cap

1

1

2

3

MPX™ PEM and PRC  

End view

Power bus

Отзывы: