1 INSTALLATION
Vertiv™ offers optional monitoring packages for the Liebert® MBX Busway System End Feed Box and Tap-
Off Box using Socomec DIRIS Digiware.
• End Feed Box Only Package: Includes DIRIS Digiware G-30, I-45 and U-30
• End Feed Box and Tap-Off Box Package: Includes DIRIS Digiware G-30, I-45, U-30, I-30 and C-31
interface module.
1.1 End Feed Box Monitoring Setup
NOTE: Before beginning to test or program any Digiware components in the Tap-Off Box, ensure that
your G-30 and U-30 Modules are configured.
For the G-30 Module ensure:
• All settings are set to default unless otherwise required by the client.
• Set the address to 1.
For the U-30 Module ensure:
• All settings are set to default unless otherwise required by the client.
• Set the address to 2.
NOTE: The addresses for the G-30 Module and the U-30 Module must not conflict.
NOTE: The G-30 must be programmed first, followed by the U-30, then any I-modules. The U-30
Module governs all I-modules’ baud rate and parity. Always check when testing I-modules that the
baud rate programmed into the U-30 carried over to the I-module.
1.2 End Feed Box Ethernet Configuration
1. Power ON the
End Feed Box
.
2. Connect the
G-30 Module
to your laptop using a standard straight through CAT5 ethernet cable.
3. Browse to
www.Socomec.us,
download and install the latest Easy Config software.
4. Click the
Change Profile Button
in the upper right corner of Easy Config.
5. Log in to the
Super User
profile using password "sOcOmec".
6. Click
Add
a Device.
7. Enter a Name for the End Feed Box.
8. Select
DIRIS G-30/G-40/G-50/G60
from the Type drop down menu.
9. Enter the IP address. The default address is
192.168.0.2.
10. Click
Save
.
11. Click
Connect To Device
.
12. Check the following settings:
a. Verify that the latest firmware is installed on the device. You can check the latest firmware
version on the "Socomec" website. If firmware needs updated, see
on page 9 for
instructions.
b. Set the IP address and set the address (Slave ID) to 1.
1 Installation
1
Содержание Liebert MBX Busway
Страница 1: ...Liebert MBX Busway System Optional Busway System Monitoring Installer User Guide ...
Страница 4: ...Vertiv Liebert MBX Monitoring Installer User Guide ii This page intentionally left blank ...
Страница 8: ...Vertiv Liebert MBX Monitoring Installer User Guide 4 This page intentionally left blank ...
Страница 12: ...Vertiv Liebert MBX Monitoring Installer User Guide 8 This page intentionally left blank ...
Страница 14: ...Vertiv Liebert MBX Monitoring Installer User Guide 10 This page intentionally left blank ...
Страница 15: ...Vertiv Liebert MBX Monitoring Installer User Guide ...