Vertiv | Liebert LVC | User Manual
13
Installation
Figure 1-10 Side by Side Installation Space Overhead View
Table 1-2 Side by Side Installation Space Requirement (unit: mm)
The quantity of installed condensers is less than 30
Model
h (engineered mounting bracket height)
h1
a
b
c
LVC088 /
LVC106
0.5≤h<1.0
①
≤1
≥1.5
0.03
②
≥1.8
≥1.0
≥1.4
LVC140
0.5≤h<1.0
①
≥2.0
≥1.0
≥1.6
LVC152 / LVC170
0.5≤h<1.0
①
≥2.2
≥1.0
≥1.8
The quantity of installed condensers between 30-50
Model
h (engineered mounting bracket height)
h1
a
b
c
LVC088 /
LVC106
0.5≤h<1.0
①
≤1
≥1.5
0.03
②
≥2.0
≥1.0
≥1.6
LVC140
0.5≤h<1.0
①
≥2.2
≥1.0
≥1.8
LVC152 / LVC170
0.5≤h<1.0
①
≥2.4
≥1.0
≥2.0