6.5.3 SNMP Folder
Folders and settings in this folder permit configuring the card for various types of SNMP communication,
including access, traps and other user settings.
SNMP Settings
SNMPv3 Engine ID
The generated SNMPv3 engine ID.
NOTE: The engine ID is based on the MAC address of the card by default.
SNMP v1/v2c Enable
Enable or Disable SNMP v1/v2c.
SNMP v3 Enable
Enable or Disable SNMPv3.
Authentication Traps
When enabled, an Authentication Trap is sent if an SNMP host tries to access the card via SNMP,
but either the host address is not in the SNMP Access Settings or it is using the wrong Community
String.
Heartbeat Trap Interval
Enable or Disable and set interval 5 minutes, 30 minutes, 1 hour, 4 hours, 8 hours, 12 hours and 24
hours.
RFC-1628 MIB
Enable or Disable support for retrieval of data from the RFC-1628 MIB objects.
RFC-1628 MIB Traps
Enable or Disable support for sending RFC-1628 traps. The RFC-1628 MIB must be enabled for
RFC-1628 traps to operate.
These traps apply only to UPS systems.
Liebert Global Products (LGP) MIB
Enable or Disable support for getting and setting data using the Liebert Global Products MIB.
LGP MIB Traps
Enable or Disable support for Liebert Global Products MIB traps. The LGP MIB must be enabled for
LGP traps to operate.
LGP MIB System Notify Trap
Enable or Disable support for the LGP System Notification trap. This is a single trap sent each time
an alarm or warning is added or removed from the conditions table. It provides a text description of
the event in a varbind of the trap message. The LGP MIB must be enabled for LGP Notify traps to
operate.
Vertiv™ | Liebert® IntelliSlot Unity Card Installer/User Guide
56