4.5.1 Setting Up Customer Input Events
Input devices must be wired to Terminal 24 through a dry contact to locations 50, 51, 55 and 56 for alarms 1 through 4
respectively, (For the terminal location, refer to the cooling unit electrical schematic and installation manual). Table 4.5
below, maps the customer input to the RADs
Customer Input
Customer Input Terminal
RAD Number
RAD Terminal
1
24
1
50
2
24
2
51
3
24
3
55
4
24
4
56
Table 4.5 Customer Input Terminals to RAD Terminals
1.
Touch
, then
>
Alarm/Event Setup
>
Remote Alarm Device Input
. The EDIT panel opens.
2.
In
Customer Input X (where X is the input number)
, select the input type that best describes the wired
device/input, see Table 4.6 on the next page.
3.
In
Customer Input X Active When
, select whether the input is active (triggers events) when
Opened
or
Closed
.
4. Once input(s) are set, touch
Save
.
The customer-input settings are saved.
Customer Input Options
Customer Input X
Selects the customer wired input, where X is the input number. See Table 4.6 on the next page, for a description of
available values.
Customer Input
X
Active When
Selects when the input triggers an event. Options are:
•
Opened: Events are triggered when the contacts across the corresponding RAD terminal strip are open.
•
Closed: Events are triggered when the contacts across the corresponding RAD terminal strip are closed.
4 Managing Events: Alarms, Warnings and Messages
53
Содержание Liebert iCOM DP400/500
Страница 8: ...Vertiv Liebert iCOM Installer User Guide vi This page intentionally left blank...
Страница 64: ...Vertiv Liebert iCOM Installer User Guide 56 This page intentionally left blank...
Страница 70: ...Vertiv Liebert iCOM Installer User Guide 62 This page intentionally left blank...
Страница 86: ...Vertiv Liebert iCOM Installer User Guide 78 This page intentionally left blank...
Страница 90: ...Vertiv Liebert iCOM Installer User Guide 82 This page intentionally left blank...
Страница 110: ...Vertiv Liebert iCOM Installer User Guide 102 This page intentionally left blank...
Страница 140: ...Vertiv Liebert iCOM Installer User Guide 132 This page intentionally left blank...
Страница 178: ...Vertiv Liebert iCOM Installer User Guide 170 This page intentionally left blank...
Страница 179: ...Vertiv Liebert iCOM Installer User Guide...