3.1.9 Automatic Fan Speed Control
Temperature sensors can control fan speed using one of three modes based on the type of sensor selected as the fan control
sensor: supply, return, or remote. See Table 3.3 below. Control is based on the selected sensor for both fan control and
temperature control and their setpoints as follows:
•
Coupled: The fan control and temperature control sensor selection is the same. When coupled, fan speed is
determined by the temperature setpoints.
•
Decoupled—the fan control and temperature control sensor selection is different. When decoupled, fan speed is
determined by the fan setpoints.
Temperature Control Sensor selected
Supply Sensor
Remote Sensor
Return Sensor
Fan Control Sensor selected
Supply Sensor
Coupled
N/A
N/A
Remote Sensor
Decoupled (Recommended) Coupled
N/A
Return Sensor
Decoupled
Decoupled
Coupled
Table 3.3 Fan Speed Controlling Sensor Ooptions
To Set Parameters for Automatic Fan Speed Control
1.
Touch
, then
>
Setpoints
>
Fan Control
,
•
Set
Fan Control Type
to
Manual
•
Select a
Fan Control Sensor
.
•
Adjust the setpoint options, then touch
Save
.
Sensor based fan speed control is set.
2.
Touch
Temperature Control
.
3.
On the TEMPERATURE CONTROL secondary panel:
•
Select a
Temperature Control Sensor
.
•
Adjust the setpoint options, then touch
Save
.
3.2 Scheduling Condenser and Cooling Unit Tasks
The Scheduler configures operating conditions and modes for specific intervals. Tasks to schedule include:
•
Condenser set back: See
Scheduling Condenser Low-noise Operation
•
Condenser fan-reversal: See
Scheduling Condenser Fan Reversal
•
Unit sleep Schedule: Turns off units during times of low demand and controlled only by temperature. Sleep is
interrupted if the return temperature rises above the alarm threshold.
3 Service Operation
31
Содержание Liebert iCOM DP400/500
Страница 8: ...Vertiv Liebert iCOM Installer User Guide vi This page intentionally left blank...
Страница 64: ...Vertiv Liebert iCOM Installer User Guide 56 This page intentionally left blank...
Страница 70: ...Vertiv Liebert iCOM Installer User Guide 62 This page intentionally left blank...
Страница 86: ...Vertiv Liebert iCOM Installer User Guide 78 This page intentionally left blank...
Страница 90: ...Vertiv Liebert iCOM Installer User Guide 82 This page intentionally left blank...
Страница 110: ...Vertiv Liebert iCOM Installer User Guide 102 This page intentionally left blank...
Страница 140: ...Vertiv Liebert iCOM Installer User Guide 132 This page intentionally left blank...
Страница 178: ...Vertiv Liebert iCOM Installer User Guide 170 This page intentionally left blank...
Страница 179: ...Vertiv Liebert iCOM Installer User Guide...