13.3 Installing Supply Control Sensors
13.3.1 Installing the Supply Air Temperature Sensor
The supply temperature sensor is connected to P8, Pins 1 and 2 at the factory require no configuration.
1.
Place the sensor in an area that is influenced only by the unit to which it is connected to provide an accurate
reading: 5 ft. to 15 ft. (1.5 m to 4.5 m) from the cooling unit, Figure 12.15 below.
NOTE: A 50 ft. (15 m) extension cable is available from Vertiv™ if the sensor must be more than 15 ft. (4.5 m) from the
iCOM unit.
2.
Confirm connectivity via SENSOR DATA. See
Figure 12.15 Placement of the Supply Air Temperature Sensor
Item
Description
1
Return air
2
Internal temperature/humidity sensor
3
Temperature sensor
4
Supply air
5
Liebert® Thermal Management unit
13 Hardware Installation
121
Содержание Liebert iCOM DP400/500
Страница 8: ...Vertiv Liebert iCOM Installer User Guide vi This page intentionally left blank...
Страница 64: ...Vertiv Liebert iCOM Installer User Guide 56 This page intentionally left blank...
Страница 70: ...Vertiv Liebert iCOM Installer User Guide 62 This page intentionally left blank...
Страница 86: ...Vertiv Liebert iCOM Installer User Guide 78 This page intentionally left blank...
Страница 90: ...Vertiv Liebert iCOM Installer User Guide 82 This page intentionally left blank...
Страница 110: ...Vertiv Liebert iCOM Installer User Guide 102 This page intentionally left blank...
Страница 140: ...Vertiv Liebert iCOM Installer User Guide 132 This page intentionally left blank...
Страница 178: ...Vertiv Liebert iCOM Installer User Guide 170 This page intentionally left blank...
Страница 179: ...Vertiv Liebert iCOM Installer User Guide...