4.4 Transferring from Normal to Bypass Mode
Press and hold the power button for 2 seconds.
If the UPS is operating normally, without faults, the option to
Turn to bypass
,
Turn off output
, or
Turn off UPS
displays:
1.
Use the arrow buttons to select
Turn to bypass
, and press
Enter
.
2.
Use the arrow buttons to select
No
or
Yes
, then press
Enter
to confirm.
If the bypass power is outside normal operating range, do not transfer to Bypass mode.
4.5 Transferring from Bypass to Normal Mode
Press and hold the power button for 2 seconds.
If the UPS is operating normally, without faults, the option to
Turn on UPS
,
Turn off output
, or
Turn off UPS
displays:
1.
Use the arrow buttons to select
Turn on UPS
, then press
Enter
.
2.
Use the arrow buttons to select
No
or
Yes
, then press
Enter
to confirm.
NOTE: The UPS automatically switches back from bypass to normal mode after an overheated or overloaded fault is
cleared and normal power is restored.
4.6 Shutting Down the UPS Completely
WARNING! Risk of electric shock. Can cause injury or death. Disconnect all local and remote electric power
supplies before working with the UPS. Ensure that the unit is shut down and power has been disconnected
before beginning any maintenance.
Transfer to Bypass mode, see
Transferring from Normal to Bypass Mode
above . Then, if power to the load is not needed, open
the main input circuit breaker or disconnect the input power cable from the input power.
4.7 Remote Emergency Power Off (REPO)
REPO turns off the UPS in case of any emergency conditions. In case of emergency, the REPO switch turns off the rectifier
and inverter and stops powering the load immediately. The battery stops charging and discharging.
To manually power off in an emergency, disconnect the terminal connecting the REPO port on the rear of the UPS.
If mains/utility power is connected to the UPS input, the UPS control circuit remains active even though output power is
disabled. To remove all mains/utility power, disconnect the external main input circuit breaker.