Vertiv™ Liebert EXS 80kVA UPS User Manual
5 UPS Operating Instructions
5.2.1. Start-up Procedures in Normal Mode
WARNING! 1. To avoid misreporting as faults, all operations relating to disconnection or
connection of the maintenance bypass switch shall be finished within three seconds.
2. After the output is closed, If any loads are connected to the UPS output terminals, check with
the user that it is safe to apply power.
Use the following procedures to switch the UPS on when it is in the fully switched off state.
1. Open the front door of the UPS, ensure that the internal maintenance bypass switch Q3 is off, and that
the input cables and PE terminals are connected securely.
2. Close the output switch Q5, bypass input switch Q2 and main input switch Q1 in turn.
3. At the moment, the system is powered on, and the UPS internal cooling fan starts. The rectifier executes
self-check and starts to run. The rectifier runs in normal state for about 30 seconds, after which the
rectifier start-up phase is complete. See
for power flow page.
Figure 5-2 Flow page
218.2V
50.0Hz
219.3V
50.0Hz
Charge
563.8V
97%
200.0 Min
8.2V
0Hz
0%
4. Finish setting up the single UPS parameters and check them.
Access the main menu screen, press the
or
key to s.elect ‘Status’, and press the
key to access
the interface shown in
.
Figure 5-3 Main menu screen
Status
Settings
Control
Log
About
Maintain
Содержание Liebert EXS 80kVA UPS
Страница 1: ...Liebert EXS 80kVA UPS User Manual...
Страница 8: ...vi Vertiv Liebert EXS 80kVA UPS User Manual This page is intentionally left blank...
Страница 12: ...4 Vertiv Liebert EXS 80kVA UPS User Manual Safety Precaution This page is intentionally left blank...
Страница 24: ...16 Vertiv Liebert EXS 80kVA UPS User Manual 1 Overview This page is intentionally left blank...
Страница 34: ...26 Vertiv Liebert EXS 80kVA UPS User Manual 2 This page is intentionally left blank...
Страница 94: ...86 Vertiv Liebert EXS 80kVA UPS User Manual 7 This page is intentionally left blank...
Страница 110: ...102 Vertiv Liebert EXS 80kVA UPS User Manual 10 This page is intentionally left blank...
Страница 119: ...111 Vertiv Liebert EXS 80kVA UPS User Manual...