Component
Type
Text Display
ID
Description
Rectifier
Status
Rectifier mains is
out of tolerance
12-005
Mains failure notification without any delay.
Rectifier
Alarm
Rectifier Input
Switch Open
22-014
—
Rectifier
Alarm
Rectifier mains
failure
22-015
Warning set after the delay defined by P1110.
Rectifier
Alarm
Wrong phase
rotation
22-017
Input line phase rotation is incorrect.
Rectifier
Alarm
DC voltage low
22-018
DC link voltage under the threshold defined by P1135.2, causing PWM inhibition.
Rectifier
Alarm
Out of
synchronization
22-020
During the rectifier running it causes the rectifier to stop temporarily.
Rectifier
Alarm
Peak Input Voltage
22-021
Mains voltage high peak detector trips when instantaneous voltage exceeded the
limit defined by P 1140.i05.
Rectifier
Alarm
Overtemperature
Phase U-A
22-061
Set when Phase U temperature is greater then P 1151 setting (Def = 80°C)
Rectifier
Alarm
Overtemperature
Phase V-B
22-062
Set when Phase V temperature is greater then P 1151 setting (Def = 80°C).
Rectifier
Alarm
Overtemperature
Phase W-C
22-063
Set when Phase W temperature is greater then P 1151 setting (Def = 80°C).
Rectifier
Alarm
Overtemperature
B Phase U-A
22-073
Set when Phase U temperature is greater then P 1151 setting (Def = 80°C).
Rectifier
Alarm
Overtemperature
B Phase V-B
22-074
Set when Phase V temperature is greater then P 1151 setting (Def = 80°C).
Rectifier
Alarm
Overtemperature
B Phase W-C
22-075
Set when Phase W temperature is greater then P 1151 setting (Def = 80°C).
Rectifier
Alarm
DC Overvoltage
22-102
Set when the rectifier detects DC bus voltage above threshold P1753.29.
Table A.2 Alarm Messages (continued)
Component
Type
Text Display
ID
Description
Battery
Fault
Battery Test
Failure
34-023
—
Battery
Fault
Battery
Overcurrent Fault
34-070
BCB Control algorithm has detected an overcurrent condition. BCB Open command
issued.
Battery
Fault
Battery Ground
Fault
34-071
Enabled by Input Function 22 BCB GND Fault. Battery ground fault detector is
tripped.
Bypass
Fault
E.P.O.
31-020
—
Bypass
Fault
Bypass hardware
failure
31-021
Output voltage is out of tolerance and the bypass input is within tolerance (SW
detected fault monitoring output signals).
Table A.3 Fault Messages
Vertiv™ | Liebert® EXL S1 Operation and Maintenance Guide
62
Содержание Liebert EXL S1
Страница 8: ...Vertiv Liebert EXL S1 Operation and Maintenance Guide 4 This page intentionally left blank...
Страница 16: ...Vertiv Liebert EXL S1 Operation and Maintenance Guide 12 This page intentionally left blank...