12. Add a compression nut to the wire—Do not tighten the nut.
13. Reconnect the wiring to the proper terminals and verify that the run jumper is in place. See
Figure 8.4 on page 36, and Figure 8.5 on the previous page, for wiring details.
•
The torque for the electrical terminals is 11.5 in-lb (1.3 Nm). Tighten the compression nut
to a torque of 22 in-lb (2.5 Nm).
14. With the PCB powered, the board display should read
F00
.
15. Press the ESC button.
16. Press the UP-arrow button once:
•
If
P- -
is displayed, perform step
17
.
•
if
P- -
is not displayed, perform steps
18
through
46
.
17. If
P- -
is displayed, press the ENT button to enter the P- - Menu.
The P- - Menu allows compact set-up/preparation of the condenser in the factory or in the
field. Use the functions described in Table 8.1 below, to establish a default control
configuration for the board.
Item
ID
Meaning
Default
Notes
P01
Enter
Preparation
Mode
0
Setting this value to ‘1’ enables preparation mode. All other ‘P—‘menu items are disabled until this
value is ‘1’. Note that control operations may be affected during preparation mode, therefore the
cooling unit should be off. Setting this value back to ‘0’ creates new default values based upon
selections in this menu. After default values are established, the board exits preparation mode and
reboots.
P02
Automatic
VSD
Configuration
1
This item should only be used to address the VSDs for the unit. The value entered indicates the
model of the VSD:
1 – EBM
2 – Ziehl-Abegg
3 – Fans Tech
All fans must be the same model to use this parameter. When
ENT
is pressed, the board will
operate and power contactors for the VSDs and assign ModBus addresses. This procedure may
take up to 5 minutes to complete.
P03
Refrigerant
Type
2
1 = R22
2 = R407C
3 = R410A
P04
Number
of Circuits
1
1 = Single Circuit
2 = Dual Circuit
P05
Liebert®
Lee Temp
Option
0
0 = No Lee Temp installed
1 = Liebert® Lee-Temp installed
P06
Condenser
1
0 = Small
Table 8.1 P-- menu items and definitions
18. Turn the power On.
19. The control board flashes
F00
on the display when it has completed its boot cycle.
20. Press the ESC button.
21. Use the UP or DOWN arrow button until
C--
displays.
22. Press the ENT button.
23. Use the UP or DOWN arrow button until
C03
displays
24. Press the ENT button.
Vertiv | Liebert® DSE500™ Installer/User Guide
38
Содержание Liebert DSE500
Страница 1: ...Liebert DSE500 Packaged Solution Thermal Management System Installer User Guide...
Страница 8: ...Vertiv Liebert DSE500 Installer User Guide 8 This page intentionally left blank...
Страница 12: ...Vertiv Liebert DSE500 Installer User Guide 12 This page intentionally left blank...
Страница 16: ...Vertiv Liebert DSE500 Installer User Guide 16 This page intentionally left blank...
Страница 24: ...Vertiv Liebert DSE500 Installer User Guide 24 This page intentionally left blank...
Страница 26: ...Vertiv Liebert DSE500 Installer User Guide 26 This page intentionally left blank...
Страница 50: ...Vertiv Liebert DSE500 Installer User Guide 50 This page intentionally left blank...
Страница 52: ...Vertiv Liebert DSE500 Installer User Guide 52 This page intentionally left blank...
Страница 54: ...Vertiv Liebert DSE500 Installer User Guide 54 This page intentionally left blank...
Страница 76: ...Vertiv Liebert DSE500 Installer User Guide...