Parameters
Description
Output assembly
AG R 1"
Top/bottom installation distance
100 mm (3.94 in)
Lateral installation distance
50 mm (1.97 in)
Environmental Conditions
Operating temperature
-25 to +40°C (-13 to +104°F)
Storage temperature
-40 to +80°C (-40 to +176°F)
Ambient humidity
0 - 95 %, no condensation
Table 9.2 Technical Data (continued)
9.3 Installation Instructions
NOTICE
The ball valve can be installed vertically or horizontally (all sides). It is not permitted to install the ball valve
suspended, i.e. with the stem pointing downwards.
Figure 9.2 Permissible Mounting Positions
9 Water Flow Modulating Valve
71