CAN ID
SW3-1
SW3-2
SW3-3
SW3-4
SW3-5
SW3-6
SW3-7
SW3-8
Note
7
OFF
OFF
OFF
ON
ON
ON
ON
ON
Subordinate
Unit 7
8
ON
ON
ON
OFF
ON
ON
ON
ON
Subordinate
Unit 8
9
OFF
ON
ON
OFF
ON
ON
ON
ON
Subordinate
Unit 9
10
ON
OFF
ON
OFF
ON
ON
ON
ON
Subordinate
Unit 10
11
OFF
OFF
ON
OFF
ON
ON
ON
ON
Subordinate
Unit 11
12
ON
ON
OFF
OFF
ON
ON
ON
ON
Subordinate
Unit 12
13
OFF
ON
OFF
OFF
ON
ON
ON
ON
Subordinate
Unit 13
14
ON
OFF
OFF
OFF
ON
ON
ON
ON
Subordinate
Unit 14
15
OFF
OFF
OFF
OFF
ON
ON
ON
ON
Subordinate
Unit 15
Table 6.3 Address Settings of CAN ID (continued)
NOTE: The iCOM Edge can connect up to 16 units. Unit CAN ID address must be set in sequence from 0 to 15.
NOTE: CAN ID 0 is master unit. Teamwork parameters only can be set in master unit and then shared to subordinate
units. Subordinate unit uploads operation status and alarms to the master unit.