Configuring the Neutral/Earth Jumper
The UPS contains an isolation transformer that generates a neutral conductor for the connected load.
The UPS is a separately-derived source and contains a neutral/earth jumper. You may need to remove a
factory-installed neutral/earth-jumper copper bar to comply with local codes and regulations.
Figure 3.19 Configuring the neutral/earth jumper
Connecting the Cables
NOTE: Input and output cables must be run in separate conduit before cable connection.
1. Remove the knockouts at the junction box, see Figure 3.20 below and pull the cables through
them, leaving some slack for installation.
Figure 3.20 Knockouts in units without a transformer