Specifications
Vertiv
| Liebert
®
EXM
™
Parallel Cabinet User Manual |
29
3.0 SPECIFICATIONS
Table 4
Liebert EXM Parallel Cabinet specifications
Model Size
10-40kVA
60-100kVA
120-200kVA
Cabinet Width
300mm
600mm
800mm
Input Parameters
Input Voltage to Bypass, VAC
208/120V or 220/127V, 3-Phase, 4-Wire
Input Current
Refer to UPS User Manual
Input Frequency
60
Output Parameters
Output Power, kW
10-40
60-100
120-200
Output Voltage, VAC
208/120V or 220/127V, 3-Phase, 4-Wire
Output Current, AAC
Refer to
Output Frequency
60
Physical Parameters and Standards
Dimensions, in. (mm)
Cabinet Width, side panels attached
11.81 (300)
23.62 (600)
31.49 (800)
Depth, in. (mm)
39.4 (1000)
Height, in. (mm)
78.74 (2000)
Weight, lb (kg)
1+1 & 2+0
263 (119.3)
—
—
1+1 & 2+0
—
594 (269.4)
—
2+1
—
594 (269.4)
—
1+1 & 2+0
—
—
686 (311.2)
2+1
—
—
714 (323.8)
Color
Black (ZP-7021)
Degree of Protection for UPS Enclosure
IP 20 (with and without front door open)
Standards and conformities
UL1778 5th Edition; CSA 22.2 107-3-14
ISTA Procedure 1H; WEEE
Minimum Clearance, Top, in. (mm)
24 (610)
Minimum Clearance, Back, in. (mm)
0
Minimum Clearance, Sides, in. (mm)
0
Cable Entrance
Top or Bottom
Environmental Parameters
Storage Temperature Range, °F (°C)
-13 to 158 (-25 to 70)
Operating Temperature, °F (°C)
32 to 104 (0 to 40) (UPS)
Relative Humidity
Maximum 95% Non-Condensing
(Operating and Non-Operating)
Maximum Altitude above MSL, ft. (m)
Refer to the UPS manual, SL-25648, SL-25650 or SL-26100.