![Vertiv APM 0250kMK16FN02000 Скачать руководство пользователя страница 101](http://html1.mh-extra.com/html/vertiv/apm-0250kmk16fn02000/apm-0250kmk16fn02000_user-manual_1008197101.webp)
5.6 Status Bar Component
The status bar indicates UPS status by:
•
Scrolling messages to inform viewers; see Table 5.1 below through Table 5.3 on page 95.
•
Changing color; green for normal, yellow for warning and red for alarm.
•
Showing an icon inside the bar; shown at right.
5.6.1 Status Bar Messages
Up to three messages may scroll through the status bar to the right of the status icon. Each message will have a duration of
four seconds, except they change immediately if the system’s status changes.
M es s ag e 1
M es s ag e 2
M es s ag e 3
D efinition
Load on inverter
Frequency converter mode
active
Output frequency X Hz
This system is in normal operating mode, supplied by
the inverter and operating as a frequency converter
Load on inverter
Energy saving mode active
/
This system is in normal operating mode, supplied by
the inverter, and has one of the energy-saving modes
active
Load on inverter
Operation normal
/
This system is in normal operating mode, supplied by
the inverter, and has no special configurations
Load on bypass
Energy saving mode active
/
This system is in normal operating mode, supplied by
the bypass , and has one of the energy-saving modes
active
Load on battery
Battery test in progress
/
This system is in normal operating mode, supplied by
the inverter via the battery, and a battery test is actively
running
Load off
Energy saving mode active
/
This system is in normal operating mode, load not
supplied by this unit, and has one of the energy-saving
modes active
Load on inverter
Test mode active
/
This system is in normal operating mode, for the test
mode that is activated
T able 5.1 N o rm al statu s m essages
5 Operator Control and Display Panel
93
Vertiv™ Liebert® APM Plus User Manual
Содержание APM 0250kMK16FN02000
Страница 1: ...Vertiv Liebert APM Plus User Manual 50 250 kVA UPS...
Страница 8: ...vi This page intentionally left blank Vertiv Liebert APM Plus User Manual...
Страница 16: ...1 Important Safety Instructions 8 This page intentionally left blank Vertiv Liebert APM Plus User Manual...
Страница 30: ...2 Overview 22 This page intentionally left blank Vertiv Liebert APM Plus User Manual...
Страница 60: ...4 Electrical Installation 52 This page intentionally left blank Vertiv Liebert APM Plus User Manual...
Страница 73: ...Figure 5 11 Customize the display 5 Operator Control and Display Panel 65 Vertiv Liebert APM Plus User Manual...
Страница 97: ...5 Operator Control and Display Panel 89 Vertiv Liebert APM Plus User Manual...
Страница 154: ...Figure 8 8 LBS port J4 on bypass control module 8 Parallel System and LBS System 146 Vertiv Liebert APM Plus User Manual...
Страница 182: ...11 Service and Maintenance 174 This page intentionally left blank Vertiv Liebert APM Plus User Manual...
Страница 188: ...12 Specifications 180 This page intentionally left blank Vertiv Liebert APM Plus User Manual...
Страница 191: ...Vertiv Liebert APM Plus User Manual...