Vertiv ALPHA 900 Скачать руководство пользователя страница 2

ALPHA 900 - 1800
Battery charger / DC Power Supply

VertivCo.com 

30 avenue Montgolfier 

– BP90 

69684 Chassieu 
France 
Tel: +33 (0)4 72 47 63 77 
[email protected] 

 

Notice : 6012559 

Révision : 03 

Version : UK 

Date : 09/05/17 

Visa : ELA

 

©  2017  Vertiv  Co.  All  rights  reserved.  Vertiv,  the  Vertiv  logo  and  Chloride  are  trademarks  or  registered  trademarks  of  Vertiv  Co.  All  other  names  and  logos 
referred to are trade names, trademarks or registered  trademarks of their respective owners. While every  precaution has been taken to ensure accuracy and 
completeness  herein,  Vertiv  Co.  assumes  no  responsibility,  and  disclaims  all  liability,  for  damages  resulting  from  use  of  this  information  or  for  any  errors  or 
omissions. Specifications are subject to change without notice. 

CONFIGURATION 

 

 

Mode selection 

– output voltage 

Position of                         Used as 

 

Mode selector                       model  

 

Charger 

Power Supply 

External  

setting 

 

 

 

 

 

 

12 V 

 

24 V 

 

48 V 

 

120/110 V 

 

240/220 V 

13.6 Vdc 

 

27.2 Vdc 

 

54.5 Vdc 

 

136.2 Vdc 

 

272.4 Vdc 

N/A 

 

N/A 

 

N/A 

 

122.6 Vdc 

 

245.2 Vdc

 

12.0 Vdc 

 

24.0 Vdc 

 

48.0 Vdc 

 

120.0 Vdc 

 

240.0 Vdc 

N/A 

 

N/A 

 

N/A 

 

110.0 Vdc

 

 

220.0 Vdc

 

0 à 15 Vdc 

 

0 à 30 Vdc 

 

0 à 60 Vdc 

 

0 à 150 Vdc 

 

0 à 300 Vdc 

 

N.B.: 

Charger

 or 

Power supply,

 values in this table are factory settings. Potentiometer U allows adjusting output voltage by roughly ±5%. 

N.B.: when terminals 10 and 11 are strapped, output voltage raises by 3,8% (Boost function)

 

 

CONFIGURATION in mode controled by supervisor QUARTZ : 

 

 

IB and U switches of selector must be 
in 

External setting

 position 

 
 
 
 

 

The terminals of ALPHA (+ Out) and 
(

– Out) must be connected at 

terminals (+) and (-) of QUARTZ 

 

 

NO strap on the terminals 8-9 

 

 

For more details, to see the note KIT 
Supervision (36048-6008052-EN) 

 

 

VERY IMPORTANT  

(in particular in case of replacement of ALPHA unit on site).

  

Above, the “Factory configuration” can be modified according to your use on site.  

For any other operating process and U & IB adjustments, to refer to the table below. 

CAUTION 

FACTORY 
CONFIGURATION 

Charger

   

VRLA  batteries 

 without 

QUARTZ supervisor

 

Mode selector

  

Output voltage U setting 

Battery current IB setting 

Mains ON led 

Mode selector 

 

(switch 1234)

 

Отзывы: