Vertiv™ NetSure™ +24V Battery Tray Kit Installation Manual
Proprietary and Confidential © 2022 Vertiv Group Corp.
2
2
Installation Procedures
2.1
Mounting the Battery Tray
Procedure
1.
To install a Battery Tray, perform the procedure in
Figure 2.1
Mounting and Securing the 588810200SK001 Battery Tray onto the Rack
Battery Tray
Rear
Angle
Bracket
Rear Angle Bracket
Cabling
Bracket
Front
Rear
1. Slide battery tray into relay rack and
secure to relay rack with 12-24 x 3/4"
thread forming hex head screws and
#10/12 ground washers (1 place per
side) or #12 flat washers (3 places per
side). (Torque to 70 in-lbs).
2. Secure rear angle brackets (both sides)
to battery tray with 1/4-20 x 3/4” bolts,
1/4” flat washers, 1/4” lock washers, and
1/4” nuts. (Torque to 84 in-lbs).
3. Secure rear angle brackets (both sides)
to relay rack with 12-24 x 3/4" thread
forming hex head screws and #10/12
ground washers (1 place per bracket)
or #12 flat washers (1 place per bracket).
(Torque to 70 in-lbs).
4. Secure cabling brackets (both sides) to
relay rack with 12-24 x 1/2" thread forming
hex head screws. (Torque to 70 in-lbs).