Vertiv
|
eSure™ Rectifier Module User Manual (UM1R482000e3)
|
Rev. M
16
Table 5:
Exchange of Information between Rectifier and Controller
Commands / signals that can be
received by the Rectifier Module
from the Controller.
Information gathered by the
Controller from the Rectifier Module.
•
Turn On/Off
•
Current Walk-in On/Off
•
HVSD (High Voltage Shutdown)
Reset
•
Current Limit Adjustment
•
Voltage Regulation
•
Input Voltage
•
Output Voltage
•
Output Current
•
Current Limit Setting
•
Temperature
•
Over Voltage Setting
•
On/Off Status
•
Fault Alarms, such as:
HVSD
Fan Fail
•
Protection Alarms, such as:
Input Voltage Protection
Inner DC Bus Voltage Protection
High Temperature Protection
•
Thermal Derating
•
AC Derating
•
AC Fail
•
Imbalance Output Current
•
Address
•
Code
•
Date
•
Software Version
•
Hardware Version
Mechanical Specifications
•
Dimensions:
a)
Millimeters: 42.0 (Height) X 84.5 (Width) X 252.5 (Depth)
b)
Inches: 1.7 (Height) X 3.3 (Width) X 9.9 (Depth)
•
Weight: 1.13 kg (2.49 lbs)
•
Indicators:
a)
Power (Green LED)
b)
Protection (Yellow LED)
c)
Alarm (Red LED)