44 Chapter 4 Maintenance
ECM3 Series Outdoor Power System User Manual
LED lamp
LED lamp amplified
Figure 4-8 Position of LED lamp
4.2.6 Replacing Micro Switch
There is a micro switch (optional) installed in the power system for monitoring the close or open status of the cabinet
door and controlling the LED lamp.
The micro switch requires no particular maintenance, just replace it when it is damaged. If the door is closed, but the
door open alarm occurs or the LED lamp is illuminated, the micro switch may have been damaged and needs to be
replaced. The position of the micro switch is shown in Figure 4-9. The replacing procedures are simple: Remove the
cover of the micro switch, loosen the two fixing screws of the micro switch, and finally you can replace the damaged
micro switch with a new one. When installing the new micro switch, remember to reconnect the signal cable and
tightly fix the cable on the screws.
Micro switch
Amplified of micro switch
Figure 4-9 Position of micro switch