If A2FU=None, it means alarm function is cancelled.  bd.Hi, bd.Lo 

t.on, t.oFF 

 

Alarm 2 mode. Refer to alarm mode section for detail. 

none, Stdy, 
Lath, St.La 

 

 

Address of controller when communication with 
master device. 

0 - 255 

 

Communication baud rate. 2.4k=2400bps, 4.8k=4800 
bps, 9.6k=9600 bps, 19.2k=19200 bps 

2.4k, 4.8k 
9.6k, 19.2k 

9.6k 

 

Code 

Description 

Range 

Default 

 

Low Scale of Linear Input 

-1999~9999(-

199.9~999.9) 

0.0 

 

High Scale of Linear Input  

-1999~9999(-

199.9~999.9) 

100.0 

 

Scaling for Linear Input 

 
1. Press the UP and DOWN keys simultaneously for 5 seco

nds to access “LnLo” 

parameter. 
2. Adjust “LnLo” setting to correspond the low scale and after adjustment press 

 key 

once to access “LnHi” parameter. 
3. Adjust “LnHi” setting to correspond the high scale and after adjustment press 

 key 

once for normal operation. 
 
 

■ ALARM FUNCTION 
Select the alarm function 

nonE 

– Alarm action off. 

Hi 

– Process high alarm with Form A contact 

Lo 

– Process low alarm with Form A contact 

diF.H 

– Deviation high alarm with Form A contact 

diF.L 

– Deviation low alarm with Form A contact 

bd.Hi 

– Deviation band high alarm with Form A contact 

bd.Lo 

– Deviation band low alarm with Form A contact 

t.on 

– On-timer with Form A contact 

t.oFF 

–Off-timer with Form A contact 

 
b noE 

– Alarm action off 

b.Hi 

– Process high alarm with Form B contact 

b.Lo 

– Process low alarm with Form B contact 

b.diH 

– Deviation high alarm with Form B contact 

b.diL 

– Deviation low alarm with Form B contact 

b.bdH 

– Deviation band high alarm with Form B contact 

b.bdL 

– Deviation band low alarm with Form B contact 

b.ton 

– On-timer with Form B contact 

b.toF 

–Off-timer with Form B contact 

Содержание VT4826+

Страница 1: ...ut failures taking place There are other options you can choose including retransmission of either the PV or SV or RS485 communications Features T C RTD selectable from front panel or as optional extra Linear Input Heating output Relay SSR or analog to be chosen when ordering Fuzzy enhanced PID Control Auto Manual Bumpless Transfer Two alarm outputs Standby and Latch mode can be combined with 8 di...

Страница 2: ... 3 AT Auto tuning LED 4 MA Manual mode LED 5 A1 Alarm 1 LED 6 A2 Alarm 2 LED 7 C1 Control 1 LED 8 C2 Control 2 LED 1 SET KEY Press once to access the next programmable parameter Press this key for 5 seconds to reset alarm timer 2 UP KEY Press to increase the set point or parameter value 3 DOWN KEY Press to decrease the set point or parameter value 4 SHIFT KEY Press the shift key for 5 seconds to e...

Страница 3: ...noise induction keep input signal wire away from instrument power line load lines and power lines of other electric equipment Connections Explained These are typical input connection drawing intended to explain the schematic symbols Now let s look at the detail included here RTD Input looks like this Thermocouple input like this mA or mV looks like this Model A B C D E a b c d VT 4826 48 48 6 100 ...

Страница 4: ... Prog Level 5 th Prog Level SET 5sec 5sec 1 When 2nd Output Cooling is not selected CPb Cti Ctd HYS2 and db parameters are not available 2 When Pb 0 0 HYS1 will be skipped 3 When CPb 0 0 HYS2 will be skipped 4 When Pb 0 0 ti td will be skipped 5 When CPb 0 0 Cti Ctd will be skipped ...

Страница 5: ...MM SS It depends on the P tnE parameter 1999 9999 00 00 99 59 10 Auto tuning is disable Auto tuning at setpoint Low PV type auto tuning This is done at 10 below SP during Auto tuning no Control is done by PID control automatically Output is manually adjusted by operator no Output percentage Adjustable when Hand is set to Yes 100 0 100 0 100 0 SOFT LEVEL Code Description Range Default Ramp rate for...

Страница 6: ...output 1 0 2000 0 0 200 0 1 Hysteresis for ON OFF control on output 2 0 2000 0 0 200 0 1 Hysteresis of alarm 1 0 2000 1 Hysteresis of alarm 2 0 2000 1 Dead band value This defines the area in which output 1 and output 2 are both active negative value or the area in which output 1 and output 2 are both inactive positive value 1000 1000 100 0 100 0 0 Set point offset This value will be added to SV t...

Страница 7: ...mal point please reconfirm the parameter 0000 000 0 00 00 0 000 0000 Output 1 control action Reverse action for heating Direct action for cooling Low limit of span or range Set the low limit lower than the lowest expected SV and PV display Full range 0 High limit of span or range Set the high limit higher than highest expected SV and PV display Full range 1000 Software filter 0 0 99 9 10 0 Time sc...

Страница 8: ...t LnHi setting to correspond the high scale and after adjustment press key once for normal operation ALARM FUNCTION Select the alarm function nonE Alarm action off Hi Process high alarm with Form A contact Lo Process low alarm with Form A contact diF H Deviation high alarm with Form A contact diF L Deviation low alarm with Form A contact bd Hi Deviation band high alarm with Form A contact bd Lo De...

Страница 9: ...en selected the alarm output and indicator latch as the alarm occurs The alarm output and indicator will be energized even if the alarm condition has been cleared unless the power is shut off When Timer function is selected PV SV timer function is available Standby and latch mode AUTOMATIC AND MANUAL OUTPUT CONTROL Automatic control is the normal mode of controller operation In automatic control m...

Страница 10: ...ints and also specify how long the cooling must stay on each time it switches on using the hysteresis adjustment 7 When using the alarm for cooling the first thing to do is select the Alarm Function that links the alarm to the setpoint by a fixed Gap You will find on your unit that the factory default is set to this so it is not necessary to change anything That is Alarm Function diF H Deviation a...

Страница 11: ...D control The auto tune process can last from several minutes up to two hours depending on the system s parameter A time out error will occur if the auto tune process cannot be completed within two hours in this case try to set the PID parameters manually Under normal circumstances if it does not complete within say 10 minutes something is wrong To abort an auto tune process simply set the paramet...

Страница 12: ...eading then when it goes out of range the ader error Auto tune time out error Set Pb ti td manually Keypad no function Keypads are locked Keypads defective Set to a proper value Replace keypads Process value unstable Improper setting of Pb Ti Td and CT Start AT process to set Pb Ti Td automatically Set Pb Ti Td manually No heat or output No heater power or fuse open Output device defective or inco...

Отзывы: