![Vermont Castings VCS300SSBI Series Скачать руководство пользователя страница 6](http://html1.mh-extra.com/html/vermont-castings/vcs300ssbi-series/vcs300ssbi-series_assembly-procedures_1005957006.webp)
6
91D0004
VCS300SSBI/500SSBI Series Assembly
CAUTION: Some parts may have sharp edges; to avoid injury, wearing gloves during assembly, lifting or
moving the grill is recommended.
NOTE:
Ensure your grill enclosure has been constructed according to the exact specifications shown in Figure . If the enclosure
is constructed of wood or other similar combustible materials, the use of the insulated jacket Model VCS3008IJ or VCS5008IJ is
required.
If you have an LP model with a 0lb cylinder stored in the enclosure, ensure there are at least two () air ventilation openings of 10
sq. inches (64.5 cm) 180 degrees apart and they are level with the cylinder valve. Another two () openings with the same dimen-
sions and distance are required to be level with the base of the cylinder. An enclosure for an LP gas cylinder shall be ventilated by
openings at both the upper and lower levels of the enclosure. The effectiveness of the opening(s) for purposes of ventilation shall
be determined with the LP gas supply cylinder in place. This shall be accompanied by one of the following:
a. One side of the enclosure shall be completely open; or
b. For a cylinder enclosure having four (4) sides, a top and a bottom and intended for installation in a built-in enclosure:
1. At least one (1) ventilation opening shall be provided on the exposed exterior side of the enclosure located within 5 in. (17
mm) of the top of the enclosure and unobstructed. The opening(s) shall have a total free area of not less than 1 in
/lb (14.
cm
/kg) of stored fuel capacity.
. At least one ventilation opening shall be provide don the exposed, exterior side of the enclosure 1 in (5.4 mm) or less from
the floor level and shall have a total free area of not less than 1/ in
/lb (7.1 cm
/kg) of stored fuel capacity. The upper edge
shall be no more than 5 in (17 mm) above the floor level.
3. Every opening shall have a minimum dimension so as to permit the entrance of a 1/8 in (3. mm) rod.
Always confirm the installation of this grill conforms with the requirements of all local codes or, in the absence of any applicable
local codes, with either the National Fuel Gas Code, ANSI Z3.1/NFPA 54, or CSA B149.1, Natural Gas and Propane Installation
Code.