VCG Sovereign Series • SA36R/SA42R • Installers Manual • 4010-259 • Rev A • 02/05/15
32
D. Mantel and Wall Projections
The combustible mantel may have a maximum depth of
12 in. (305 mm), positioned 12 in. (305 mm) above the
fireplace opening. Combustible trim pieces that project no
more than 1-1/2 in. (38 mm) from the face of the fireplace
can be placed no closer than 6 in. (152 mm) from the top
of the fireplace opening. Combustible trim must not cover:
• the metal surfaces of the fireplace
• where the non-combustible board is placed over the
metal surfaces
• the space between the metal face of the fireplace and
framing members
Mantel
6 ft (1829 mm)
minimum
base of fireplace
to ceiling
Combustible Wall
2 x 4 stud wall
Standoffs
Measured from top of fireplace opening
12 in./305 mm
1 1/2 in./38 mm
maximum
12 in./305 mm
minimum
6 in./152 mm
minimum
Combustible
Decorative Facing
Seal joint with
non-combustible
sealant
Non-combustible
Decorative Facing
such as:
Steel, iron, brick,
tile, concrete, slate,
glass, plasters.
Grid represents 1 in. squares
Figure 7.12 Mantel Specifications