Radiance Direct Vent Gas Heater 

20012697

Installation Requirements

The installation must conform with local codes or, in 
the absence of local codes, with the National Fuel Gas 
Code, ANSI Z223.1/NFPA 54 - latest edition. (EXCEP-
TION:  Do not derate this appliance for altitude.  Main-
tain the manifold pressure at 3.5” w.c. for Natural Gas, 
and 10” w.c. for Propane).

In Canada, installation must be in accordance with the 
current CSA B-149.1 Installation Codes and/or local 
codes.  

The installation should be done by a qualified ser-
vice person who is familiar with the building codes 
and installation techniques appropriate for your 
area to accomplish a safe and effective installation.

Your dealer or your local gas supplier will be able to 
refer a qualified service person.

WARNING:    Due  to  high  temperatures,  the 
HEATER should be located out of traffic and 
away from furniture and draperies.

The surface of the Heater Is hot when it is in use. 
Young children should be watched carefully when 
they are in the same room when the Heater is in 
use, and they should be taught to avoid the hot 
surface.  Keep any objects that can burn well away 
from the Heater, and observe the recommended 
clearances that follow.

ST207a

A. Flat on corner wall
B. Room Divider
C. Island

D. Cross Corner
E. Flat on wall

Fig. 2  

 Possible stove locations.

Direct Vent System Only

A

B

E

C

D

ST207a

Stardance

Stove locations

9/28/00   djt

Clearance Requirements

Minimum Clearances to Combustible Materials

Measure side clearances as shown in Figures 3, 4 and 
5 from the outer edge of the cast iron stove top. Mea-
sure rear clearances from the outermost surface of the 
steel rear skirt.
The Radiance heater is approved for installation into 
an alcove constructed of combustible materials to the 
dimensions and clearances shown on the next page.
The same clearances apply in a standard parallel instal-
lation.

WARNING:

•  Always maintain required clearances 

(air spaces) to nearby combustibles 

to prevent fire hazard. Do not fill air 

spaces with insulation. All venting components 

must maintain  a 1” (25mm) clearance to com-

bustible materials. Maintain a 6” (150mm) clear-

ance when using single wall pipe.

•  The gas appliance and vent system must be 

vented directly to the outside of the building 

and never be attached to a chimney serving a 

separate solid fuel or gas-burning appliance. 

•  Refer to the manufacturer’s instructions includ-

ed with the venting system for complete instal-

lation procedures.

�������

���������

�����

������������

������������

������

�������������

�����

���������������

���������������

Locating The Stove

In choosing a location for the stove, consider:

• 

The location of outside walls;

• 

Where additional heat is needed:

• 

Where family members gather most often;

• 

The vent system requirements. 

NOTE: 

We do not recommend the use of wallpaper 

next to this stove. Over time, radiant heat may cause 
the wallpaper to shrink, or may adversely affect the 
binders in the wallpaper adhesive. 

Содержание Radiance RADVTBB

Страница 1: ... fire department DO NOT STORE OR USE GASOLINE OR OTHER FLAMMABLE VAPORS AND LIQUIDS IN THE VICINITY OF THIS OR ANY OTHER APPLIANCE This appliance may be installed in an after market permanently located manufactured mobile home where not prohibited by local codes This appliance is only for use with the type of gas indicated on the rating plate This appliance is not convertible for use with other gas...

Страница 2: ...mbly Procedures Tools Required 15 Parts Bag Contents 15 Unpack and Assemble Legs 15 Install Optional Fan 16 Venting System Assembly Direct Vent 17 Install Vent Adapter Pipe CFM Corporation Components 17 Install Vent Adapter Pipe Simpson Dura Vent Components 17 Install Vent Adapter Pipe Selkirk Corporation Components 18 Side Wall Termination Assembly 18 Vent Termination Below Grade 20 Vertical Thro...

Страница 3: ...ustion The Direct Vent system permits the gas appliance to be vented directly to the outside atmosphere through the side of the house or vertically through the roof Conventional venting systems Natural Vent take air from the room for combustion and vent the exhaust vertically through the roof to the atmosphere This appliance is approved for bedroom installations in the U S and Canada This applianc...

Страница 4: ...ed gas fueled heating appliance or equipment The sign shall read in print size no less than one half 1 2 inch in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OBSTRUCTIONS Inspection The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation unless upon inspection the inspector observes carbon monoxide detectors and signage instal...

Страница 5: ...et Supply Inlet 11 279 mm 13 340 mm See Page 7 for Flue Collar Centerline Dimensions Fig 1 Radiance dimensions Radiance Direct Vent Stove Dimensions Proposition 65 Warning Fuels used in gas woodburning or oil fired appliances and the products of combustion of such fuels contain chemicals known to the State of Cali fornia to cause cancer birth defects and other reproductive harm California Health Sa...

Страница 6: ...s Direct Vent System Only A B E C D ST207a Stardance Stove locations 9 28 00 djt Clearance Requirements Minimum Clearances to Combustible Materials Measure side clearances as shown in Figures 3 4 and 5 from the outer edge of the cast iron stove top Mea sure rear clearances from the outermost surface of the steel rear skirt The Radiance heater is approved for installation into an alcove constructed...

Страница 7: ...99 mm Simpson DuraVent Pipe ST131b Fig 5 Minimum wall centerline Direct Vent Only Hearth Requirements The Radiance Heater must be installed on rigid flooring When the heater is installed directly on any combustible surface other than wood flooring a metal or wood panel extending the full width and depth of the unit must be used as the hearth There are no other hearth require ments needed for install...

Страница 8: ...or LP gas must be in accordance with the current ANSI Z223 1 NFPA 54 and or local codes having jurisdiction In Canada please consult provincial and or local authorities having jurisdiction for installations at elevations above 2 000 feet 610 m for natual gas and 4 500 feet 1 370 m for LP gas WARNING Improper installation adjustment alteration service or maintenance can cause in jury or property da...

Страница 9: ...estrictor plate to slide up or down Fig 9 A guide for usage is shown in Figure 10 NOTE Some installations may require some adjust ment by the installer for optimum flame appearance Optimum flame appearance is a flame that is not sub ject to tall dirty yellow flames producing soot or flames lifting off of the ember bed ports Restrictor Plate Adjustment 1 Remove the screw in the back wall of the firebox 2...

Страница 10: ...keep in mind are shown in Figure 11 Important All vent clearances must be maintained Check your vent termination clearances against Figures 11 through 13 The vent should be placed so that people cannot be burned by accidentally touching the vent surfaces when the stove is operating The vent termination should be located where it cannot be damaged by such things as automobile doors lawn mowers or s...

Страница 11: ...let 3 91cm 3 91cm J Clearance to nonmechanical air supply inlet 6 15cm for appliances 10 000 6 15cm for appliances to building or the combustion air inlet to any Btuh 3kW 12 30cm for 10 000 Btuh 3kW 9 other appliances appliances 10 000 Btuh 3kW and 23cm for appliances 10 000 100 000 Btuh 30kW 36 91cm Btuh 3kW and 50 000 Btuh for appliances 100 000 Btuh 30kW 15kW 12 30cm for appliances 50 000 Btuh ...

Страница 12: ...on vinyl sidewalls Min 12 305 mm for vinyl sidewalls O 8 2 4 m Min O P 584 15 No of Caps DMin CMax 1 3 914 mm 2 x DActual 2 6 1 8 m 1 x DActual 3 9 2 7 m 2 3 x DActual 4 12 3 7 m 1 2 x DActual DMin of Termination caps x 3 CMax 2 termination caps x DActual NOTE Termination in an alcove space spaces open only on one side and with an overhang is permitted with the dimensions specified for vinyl or non...

Страница 13: ...S Flashing 0 12 6 12 46DVA F6 Flashing 6 12 12 12 46DVA F12 Steel Chimney Conversion Kit Kit A 6 8 46DVA KCA Kit B 6 10 46DVA KCB Kit C 6 13 46DVA KCC Masonry Chimney Conversion Kit 46DVA KMC Vertical Termination Cap High Wind 46DVA VCH Vertical Termination Cap Low Profile 46DVA VC Included in Minimum Horizontal Vent Kit 2792 All DuraVent Straight vent pipe sections have a net length 1 37mm less th...

Страница 14: ...norkel Termination 7TDVSNORK Vertical Termination Kit 1 12 6 12 Pitch 7TDVSKVA 1 Combination Horizontal Offset Roof Support 1 Vertical Termination 1 Storm Collar 1 1 12 6 12 Flashing 1 Finishing Plate CG 1 Finishing Collar CG 1 Polished Brass Flue Pipe Ring 1 Hardware Package Vertical Termination Kit 7 12 12 12 Pitch 7TDVSKVB 1 7 12 12 12 Flashing and all of the other Vertical Termination parts Ve...

Страница 15: ... beginning assembly 1 Slide stove to the rear of the pallet just far enough to access rear leg holes Make sure the stove does not tip over backwards Fig 13 2 Attach the rear legs using 3 8 hex head bolts and flat washer supplied Tighten with a 9 16 wrench or socket 3 Carefully tip the stove onto its rear legs Adjust the pallet to allow access to one of the front leg holes Be sure to leave the palle...

Страница 16: ...n RF models only WARNING This appliance is equipped with a three prong grounded plug for your protection against shock hazard and should be plugged directly into a properly grounded three prong receptacle Do not cut or remove the grounding prong from this plug 2 Remove the rear shroud panel Fig 17 and fasten the blower assembly to the firebox back with the two bolts provided Fig 17 NOTE Steps 3 and...

Страница 17: ...oles on the pipe with the holes on the flue collar of the firebox Fasten the pipe to the holes in the flue collar with the 12 x 1 2 sheet metal screws provided Fig 21 2 Dry fit the Inner Pipe assembly to the stove for the purpose of determining the center line of the pipe on the wall Side Wall Terminations Dry fit the outer elbow with the vertical outer vent and confirm the centerline alignment with the...

Страница 18: ... silicone For units factory equipped with appliance adapters from other brands of Direct Vent systems it is permissible to simply slide a length of DT pipe over the appliance adapter Secure with a minimum of two 8 x 1 4 sheet metal screws and seal with hi temp silicone Side Wall Termination Assembly 1 Locate the vent opening on the wall Refer to Page 7 Figure 5 to determine the opening centerline ...

Страница 19: ...lar up against the wall plate to cover the screws Fig 28 10 For both CFM and DuraVent Systems Install the vent terminal Fig 29 Apply high temperature seal ant one inch from the ends of the inner and outer collars Guide the inner and outer vent termination collars into the adjacent pipes Double check that the vent pipes overlap the collars by 2 Fasten the termination to the wall with the screws pro...

Страница 20: ...the snorkel Fasten the brackets to the wall first and then fasten to the snorkel with self tapping 8 x 1 2 sheet metal screws Extend the vent pipes out as far as the protruding wall face Fig 31 ST219 snorkel detail Recessed Wall Sheet Metal Screws and Bracket Wall Screws and Anchors Waterproof Seal Around Pipe ST219 Fig 30 Use extension brackets to mount snorkel against recessed wall Firestop Finis...

Страница 21: ... AAV The appliance adapter AAV adapts DIRECT TEMP to most direct vent appliances incorporating outlet collars configured to receive most common 4 ID 6 OD or 5 ID by 8 OD Twist Lock Style direct vent sys tems The adapter incorporates two 2 indentations on the outer wall of the inlet end which are designed to Twist Lock into place upon attachment to the appliance outlet Align the adapter indentations...

Страница 22: ... to provide a finished appearance once in stalled Fig 35 Ceiling Support Plate Ceiling Support Collar Trim Plate ST923 Fig 35 Ceiling support Fig 36 Selkirk Venting Components Vent Termination VC Storm Collar SC Roof Flashing AF Ceiling Support CS Trim Plate TP Pipe Length Pipe Length Appliance Adapter AAV ST924 Vertical Venting Pipe Length Appliance Adapter AAV 90 Elbow EL90 Pipe Length Trim Plate...

Страница 23: ...very 4 122 cm of pipe This can be done with the use of plumbers strapping or the offset support Adjustable Length AJ An Adjustable Length is available to accommodate installations where non standard lengths are necessary The adjustable length telescopes down over a standard length of pipe and provides an extension range of 3 89 mm to 10 267 mm Install by sliding the inlet end of the adjustable len...

Страница 24: ... combustible wall 5 If required install the outside half of the wall thimble WT through the opening and screw or nail in place Fig 41 Seal around the perimeter of the thimble face plate on the exterior wall using an RTV silicone sealant to provide protection from possible rain infiltration Fig 41 NOTE The wall thimble accommodates wall thickness es of 4 114 mm to 7 191 mm If a larger range is neede...

Страница 25: ...small weight attached to a string Hold the plum bob from the ceiling moving it until it lines up with the centerline of the outlet of the appli ance Mark the position on the ceiling NOTE Frame openings to the dimensions specified in the framing table for the cathedral ceiling support box CCS the ceiling support SC and wherever the firestop spacer FS is being used 3 Cut and frame the appropriate size...

Страница 26: ...ound and under the perimeter of the flashing where it is in contact with the roof Secure the flashing with roofing nails Finish roofing around the pipe covering the sides and upper ares of the flashing base with roofing material How ever be sure the lower unnailed portion of the base covers the roofing material 14 Position the storm collar around the pipe and slide down until it is in contact with the fla...

Страница 27: ... for Front Right Log LG487 Figure 49 Figure 50 Front Left Log Front Right Log LG489 3 Install the front left and right logs Fig 50 by placing them on the ribs shown in Figure 49 Make sure the logs line up with the flat spots on the ember bed intended for location purposes Fig 49 4 Install the left cross log by engag ing the hole on the bottom with the pin on the left side of the rear log Set front ...

Страница 28: ...alve must be disconnected from the gas supply piping during any pressure testing of that system at test pressures in excess of 1 2 psig 3 5 kPa The Radiance Heater must be isolated from the gas supply piping system by closing its indi vidual manual shutoff valve during any pressure testing of the gas supply piping system at test pressure equal to or less than 1 2 psig There must be a gas shutoff b...

Страница 29: ...e stove to complete assembly Thermostat Wire Gauge Maximum Run 18 20 feet 16 20 40 feet 14 up to 60 feet Operation 1 Install the wall thermostat in the desired location and run the wires to the stove location Terminate these leads with 1 4 female connectors 2 Connect the thermostat wires to the valve Fig 53 The Radiance is operated with the front plate in place with the doors open or closed To ope...

Страница 30: ... for SIT valve LO H I FP390 FLAME ADJUSTMENT KNOB 11 21 96 Turn counterclockwise to increase flame height Turn clockwise to decrease flame height Follow regular maintenance procedures as described on Page 41 CO105d Pilot flame 6 07 djt CO105d PSE Pilot SIT Pilot Fig 56 Correct pilot and burner flame appearance LG491 RADVTC Series Comfort Control Models RADVT Series Flame Characteristics It is impor...

Страница 31: ...l all around the heater area for gas Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor WHAT TO DO IF YOU SMELL GAS Do not try to light any fireplace Do not touch any electric switch Do not use any phone in your building Immediately call your gas supplier from a neigh bor s phone Follow the gas supplier s instruc tions To Turn Off Gas To Heater Lighti...

Страница 32: ...pilot burner assembly utilizes both a thermocouple and a thermopile The thermocouple operates the main valve operation On and Off Clean and or adjust pilot for maximum flame impingement on thermopile and thermocouple Turn valve knob to Pilot Maintain flow to pilot millivolt meter should read greater than 10mV If the reading is okay and the pilot does not stay on replace the gas valve NOTE An interru...

Страница 33: ...an will be at the highest fixed speed The transmitter will control the fan only Shut Off Procedure If the manual switch is in the REMOTE position the transmitter can shut off the main burner and fan How ever the control is still on and a command from the transmitter can turn on the main burner or fan To shut off the system turn the pilotstat knob clockwise to the OFF position This action closes the...

Страница 34: ... for recognition process to occur between the receiver valve and transmitter 3 Use functions as described in TRANSMITTER sec tion Troubleshooting 1 Locate LED light on valve 2 LED will blink after every valid command received by the transmitter this is not an error 3 Failure codes may occur anytime after pilot burner is lit 4 Sequence is failure code followed by light not blink ing for 30 seconds ...

Страница 35: ...inute wait period Cycle switch once and leave in remote Press any key on transmit ter for recognition operation Local Path Move switch from local to remote Press any key on transmitter Move switch back to local Yes If the manual switch is set to REMOTE press the mode but ton to display ON does transmitter con trol the main burner and fan Does transmitter change levels of flame height fan speed Set ...

Страница 36: ... the room and temperture setting If the settings is above room temperture on the transmitter does the main valve and fan turn on Turn pilotstat knob to OFF to turn valve com pletely off Auto Path Move switch from LOCAL to REMOTE Press any key within 30 seconds Yes Yes No No If the settings is below room temperture on the transmitter does the main valve and fan turn off ...

Страница 37: ... to disengage from the stove body Page 26 Fig 46 2 Undo the right and left latches at the top of the glass frame Page 26 Fig 47 3 Pull the top edge of the glass and frame assembly away from the firebox face Place the assembly out of the way on a flat padded surface such as a coun ter protected by a towel 4 Remove the logset from the firebox Valve Conversion RADVT Series Models 1 Turn control knob to ...

Страница 38: ...P FP1037b Fig 66 Depress and turn center plunger Valve 4 Insure manifold pressure remains between 3 2 3 5 w c for NG and 9 5 10 w c for LP To adjust the manifold pressure for NG using a Torx 10 key turn the blue screw clockwise to increase the manifold pressure Turn the screw counterclockwise to de crease the pressure Use the red screw to adjust LP 5 Replace motor top cap Pilot Orifice Conversion 1...

Страница 39: ...5 The air shutter setting is 1 2 13 mm from the orifice bracket to the edge of the air shutter 4 Install conversion orifice Refer to Table 2 5 The air shutter is factory set according to Table 3 and should not need adjustment The air shutter opening may be verified by measuring as shown in Figure 75 CO145 Fig 74 Use two wrenches to avoid damage to manifold All Models 1 Replace burner making sure vent...

Страница 40: ...Input BTU h Model Kit Orifice Part Minimum Maximum RADVT 20012899 RADVTC 20012902 31 0 120 20006927 25 000 38 000 Conversion to LP Input BTU h Model Kit Orifice Part Minimum Maximum RADVT 20012729 RADVTC 20012900 1 75 mm 20012946 25 000 36 000 LP models do not need re orificed up to 4500 1 370 m above sea level 5 Replace glass and stove front 6 Restore gas to system and relight appliance accord ing t...

Страница 41: ...stove paints available through your local dealer to touch up areas as needed Clean areas to be painted with a wire brush and be sure to cover the logs burner and valve assembly glass and frame assembly Apply the paint sparingly two light coats of paint will give bet ter results than a single heavy coat Clean porcelain enamel surfaces with a soft damp cloth Do not use abrasive cleaning agents If ne...

Страница 42: ... gasket ends Fig 78 4 Apply a thin bead of high temperature silicone rubber sealant along the inside corner of the glass frame all around the perimeter Place the flat gasketed side of the glass panel back into the steel frame Pinch the rounded inside facing gasket material to bulk it up 5 Replace the glass frame and front panel as previ ously described Inspect the Vent System Annually Have the vent...

Страница 43: ...K BLK WHT ST153 rdv connections diag 10 99 Fig 81 Fan circuit MOTOR SNAPSTAT ON OFF RHEOSTAT WHT WHT BLK BLK BLK GRN BLK ST236 FK26 wiring diagram 12 99 Schematic Diagram ST236 ST153 Wiring Diagrams ST124c Fig 80 On off switch and optional thermostat circuit Optional Thermostat Wiring On Off Switch Wiring ST124b OFF ON Thermostat Optional Thermopile Black Black Millivolt Gas Valve St124b on off sw...

Страница 44: ...5 38 19 17 18 24 46 41 1 1c 1b 1e 1d 2 50 51 52 CFM Corporation reserves the right to make changes in design materials specifications prices and discontinue colors and products at any time without notice Radiance Direct Vent Gas Heater Models RADVT Series RADVTCB RADVTEB RADVTMB RADVTBS RADVTCH RADVT VG RADVTBD RADVTBB RADVTC Series RADVTCG RADVTGG RADVTSG RADVTCCB RADVTCEB RADVTCMB RADVTCBS RADVTC...

Страница 45: ...me Glass 1409112 15 Gasket Glass Med Knit 1203702 16 Glass GFP Firebox 1601290 17 Wood Handle 1600664 18 Pan Hd Sl 1 4 20 x 3 Z 1201310 19 Brushed Nickel Insert 30002714 20 Control Door Handle Assembly 30002730 21 Washer Flat 1 4 Blk 266 x 629 064 1202473 22 CS Hex Hd 1 4 20 x 5 8 Blk 1201372 23 Latch Front Door 30001249 24 FK26 Fan Subassembly RADVTC Series Only 30000879 25 Valve Nova SIT820 852 ...

Страница 46: ...t Piezo Ignitor not shown 20012939 40 Manifold Assembly 20012202 41 Air Shutter Assembly 20012204 42 Trim ON OFF Switch 30000874 43 Transmitter Honeywell RF 20002047 44 Antennae Honeywell 395783 1 20003561 45 Wire w Straight Term 2 End 50 10002582 46 Sensor 2450 CMG 8184 0032 10002013 47 Gasket Base Pan 20004287 48 Gasket HE Door 1203687 49 Gasket Cement 3 oz Tube not shown 1206122 50 Restrictor P...

Страница 47: ...416 30001418 30001417 30001419 30001772 RADVTCBD Chestnut RADVTCH 30003253 30003248 30003247 30003249 30003251 30003250 30003252 30003254 Brown RADVTCCH Ebony RADVTEB 30003262 30003257 30003256 30003258 30003260 30003259 30003261 30003263 RADVTCEB Midnight RADVTMB 2371194 30001777 30001776 30001424 30001426 30001425 30001427 30001778 Blue RADVTCMB Vermont RADVTVG 30003271 30003266 30003265 3000326...

Страница 48: ...at control Screen Kit An optional screen R40SK for use with the operable doors is available to allow the doors to be left in the open position Warming Shelf Warming shelves add versatility to your stove they can be used to keep foods warm at mealtime Model Color 1560 Classic Black 1555 Biscuit 1556 Chestnut Brown 1557 Ebony 1558 Vermont Classic Green 1562 Sand 1565 Bordeaux 1566 Forest Green 1567 ...

Страница 49: ...49 Radiance Direct Vent Gas Heater 20012697 ...

Страница 50: ...5050 Radiance Direct Vent Gas Heater 20012697 ...

Страница 51: ...related repair charges relating to the cost and expenses of replacing or repairing defective components under the Limited Lifetime Warranty are not covered except as provided for under the Basic One Year Warranty Any part or component replaced under the provisions of this warranty is covered for six months or the remainder of the original warranty whichever is longest Anyinstallation labor constru...

Страница 52: ...2695 Meadowvale Blvd Mississauga Ontario Canada L5N 8A3 800 668 5323 www cfmcorp com CFM Corporation ...

Отзывы: