Vermont Castings Intrepid INDVR Series Скачать руководство пользователя страница 18

18

20012761

NOTES:

1. The four (4) wood 

screws provided 

should be replaced 

with appropriate 

fasteners for use 

on brick, block, 

concrete or other 

types of sidings.

2. For buildings with 

vinyl siding or 

stucco, another 

component must 

be used between 

the horizontal 

termination cap and 

the wall surface. 

The vinyl siding 

standoff prevents 

excessive heat from 

possibly melting 

the vinyl siding material. Vinyl siding standoffs are not 

required with snorkels. For vinyl wall installations a 

4-piece vinyl siding standoff should be assembled and 

installed between the horizontal termination cap and the 

exterior wall. (Figure 30) The vinyl should be cut away to 

the outer edges of the assembled standoff.

ST982
simp vinyl sidind
8/07

Cut Back 

Siding

4 pc. Vinyl Siding 

Standoff

Wood Screws 

(4 Req.)

Round 

Cap

Sconce 

Cap

Wood Screw

Figure 30

IMPORTANT:

 You must attach the four (4) pieces of the 

new vinyl siding standoff to the horizontal termination 

cap in specific order to ensure a weather tight fit. Loosely 

assemble the four parts, in order, around the base of the 

horizontal  termination  cap.  Place  the  first  of  four  pieces 

along the upper edge of the cap, then using two (2) screws 

per side, secure each piece to the pre-drilled holes along 

both sides of the cap, finally, attach the final piece to the 

bottom edge of the cap. Tighten all screws and mount cap, 

with all four (4) pieces attached, directly onto the wall with 

the four (4) 2

1

2

" (64 mm) screws provided. (Figure 30)

12” (305 mm) 

Minimum

St980 
simp snork drain 
8/07 

4” (102 mm)

Snorkel

Figure 28

Step 4.

 Position the horizontal termination cap in the center 

of the square framed hole, and attach to the exterior wall 

with the four (4) wood screws provided. Before attaching 

the vent termination cap to the exterior wall, run a bead of 

non-hardening silicone sealant around the outside edges to 

make a seal between the cap and the wall. The arrow on the 

vent cap should be pointing up. Ensure proper clearances 

to combustible materials are maintained. (Figure 29)

12” (305 mm)

Minimum

ST979 
simpson snorkel 
8/07 

4”

(102 mm)

Snorkel

Figure 27

2. The location of the horizontal vent termination on an 

exterior wall must meet all local and national building 

codes, and must not be easily blocked or obstructed. 

Refer to Pages 10 and 11 for proper Termination Clear-

ances. 

For installations requiring a vertical rise on the exterior of 

the building, 14” (356 mm) and 36” (914 mm) tall snorkel 

terminations are available. (Figure 27) Follow the same in-

stallation procedures as used for standard horizontal termi-

nations. If the snorkel termination must be installed below 

grade level, (i.e. basement application), proper drainage 

must be provided to prevent water from entering the snorkel 

termination. (Figure 28) Do not attempt to enclose the snor-

kel within the wall or any other type of enclosure.

HOT

ST981
SIMP termination
8/07

Wood 

Screws

Figure 29

Содержание Intrepid INDVR Series

Страница 1: ...use any phone in your building Leave the building immediately Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier c...

Страница 2: ...mination Clearances 12 Installation Install Optional FK20 Fan Kit 13 Venting System Components 14 Venting System Assembly General Information Options Planning 15 Rear Vent 16 Horizontal Installation 1...

Страница 3: ...S and Canada This appliance may be installed in an aftermarket manufactured mobile home where not prohibited by state or local codes WARNING Operation of this heater when not connected to a properly i...

Страница 4: ...for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half 1 2 inch in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OBSTRUCTIONS In...

Страница 5: ...mm 13 352 mm 21 553 mm 16 418 mm 21 543 mm 18 457 mm Centerline of Flue Pipe 12761 Intrepid DV dimensions 6 07 6 165 mm C L Valve Inlet 4 102 mm C L Valve Inlet Stove Dimensions Intrepid Direct Vent G...

Страница 6: ...local gas supplier will be able to refer a qualified service person A B C D ST936 Stardance rear vent Stove locations 6 07 djt Figure 2 Possible stove locations Clearance Requirements Minimum Clearan...

Страница 7: ...learance and Flue Centerline Figure 4 Corner installation minimum corner clearance and flue centerline Wall and Ceiling Clearances 9 230 mm Max Mantel Width Refer to Fig 6 4 102 mm Sidewall Trim 2 63...

Страница 8: ...45 elbows may be substituted for each single 90 elbow With a rise between 2 5 one 90 or two 45 elbows may be used Excluding the first elbow directly off the back of the unit 20 19 18 16 15 14 13 12 1...

Страница 9: ...strictor Plate Vertical terminations must be within this area Unacceptable Venting Configuration No Restrictor Plate Figure 8 Vertical vent termination window Restrictor Plate Adjustment for Extended...

Страница 10: ...the distance limitations of the venting system Vent Termination Clearances Your stove is approved to be vented either through the side wall or vertical through the roof VermontCastingsGroupdoesnotrequ...

Страница 11: ...h for appliances 100 000 Btuh 30kW 15kW 12 30cm for appliances 50 000 Btuh 15kW K Clearance to a mechanical air supply inlet 6 1 83m 3 91cm above if within 10 3m horizontally L Clearance above paved s...

Страница 12: ...n 12 305 mm for vinyl sidewalls O 8 2 4 m Min O P V V V No of Caps DMin CMax 1 3 914 mm 2 x DActual 2 6 1 8 m 1 x DActual 3 9 2 7 m 2 3 x DActual 4 12 3 7 m 1 2 x DActual DMin of Termination caps x 3...

Страница 13: ...rs located on top of the firebox are properly seated on the gasket The doors sit flush on the gasket and should lift easily from the seal around the opening Unpack the Stove The stove is shipped fully...

Страница 14: ...k 46DVA 06B 9 Straight Blk 46DVA 09B 81 2 Pipe Extension Blk 46DVA 08AB 16 Pipe Extension Blk 46DVA 16AB 12 Straight 46DVA 12 Venting System Components Use the wire tie to secure the fan and rheostat...

Страница 15: ...installations Horizontal Termination Figs 18 and 19 Vertical Terminations Figure 20 When planning your installation it will be necessary to select the proper length of vent pipe for your particular r...

Страница 16: ...Page 14 under Basic Straight through the Wall Installation for an installation where the heater is parallel to the wall and the vent system extends straight back through that wall 1 Locate the vent op...

Страница 17: ...tal run of venting must be level or have a 1 4 6 mm rise for every 1 305 mm of run toward the termination Never allow the vent to run downward A downward slope can trap heat and become a possible fire...

Страница 18: ...s and mount cap with all four 4 pieces attached directly onto the wall with the four 4 21 2 64 mm screws provided Figure 30 12 305 mm Minimum St980 simp snork drain 8 07 4 102 mm Snorkel Figure 28 Ste...

Страница 19: ...connections are in their fully twist locked position ST984 straight up locat 8 07 Mark Location Mark and Drill Plumb Bob Figure 33 ST983 wall thimble cover 8 07 Sheet Metal Screws Wall Thimble Cover...

Страница 20: ...rough the roof Use a non hardening sealant be tween the roof flashing and the roofing to prevent water leakage Secure the base of the roof flashing to the roof with roofing nails Ensure the roofing ma...

Страница 21: ...r appropriate insulation level then attach the collar at the top of assembly Figure 39 For vaulted ceilings the attic insulation shield cannot be installed To prevent building insulation and other deb...

Страница 22: ...ss AMetalChimneyorMasonryChimney to a Direct Vent System Application These instructions apply to the DuraVent Direct Vent Conversion kits for factory built Class Ametal chimneys and masonry chimneys T...

Страница 23: ...himney with appropriate black direct vent pipe and an adjustable length section Atypicalconversionofanexistingmasonrychimneyisshown in Figure 45 For installation through the wall of an existing masonr...

Страница 24: ...r 0987K Existing Metal Chimney System 4 Aluminum Flex Pipe Retro Connector 0909B Any Black Di rect Vent Pipe Plus an Adjust able Length to Make a Proper Connector ST995 colinear chimney 8 07 Vertical...

Страница 25: ...0 onto the adapter Figures 47 and 48 5 Pull the flex pipe down through the ceiling support box until it protrudes approximately 3 76 mm Connect the flex pipe to the retro connector by slipping it into...

Страница 26: ...and the retro connector may be completed with sections of black direct vent pipe together with an adjustable length Installation Instructions for Converting a Masonry Chimney IMPORTANT The existing m...

Страница 27: ...h a brush no larger than 1 25 mm Never apply soap and water solution with a spray bottle Do not use an open flame for leak testing This appliance should only be connected by a qualified gas technician...

Страница 28: ...ut opening in rear shroud 4 Attach wires to valve terminals Figure 56 ST1120 Switch As sembly Screw Wire Harness Figure 55 Attach switch assembly to rear shroud ST228 attach switch wires to valve 12 9...

Страница 29: ...assembly Figure 58 Gently push right side of log back until it contacts thermopile on pilot assembly 2 Place the left front log on the pin locator on ember bed Position the log over the air inlet hole...

Страница 30: ...ular maintenance procedures as described on Page 37 Flame Temperature Adjustment For stoves equipped with HI LO valves flame adjustment is accomplished by rotating the HI LO adjustment knob located ne...

Страница 31: ...control knob extensions have been included in the finish bag These may be installed on the appropriate knob by aligning the notch on the existing knob Figure 62 with the tab on the inside of the exten...

Страница 32: ...e remote to OFF or set thermostat to lowest level 4 Open control access panel 5 Pushingascontrolknobslightlyandturnclockwise to OFF 6 Remove glass door before lighting pilot See Glass Frame Removal se...

Страница 33: ...he gas valve NOTE An interrupter block not supplied must be used to conduct this test 3 Pilot burning no gas to main burner A Wall switch or wires defective Check wall switch and wires for proper conn...

Страница 34: ...32 or 4 mm Allen wrench into the hexagonal key way of the screw Figure 69 rotate it counterclockwise until it is free and extract it 5 Check that the screw is clean and if necessary remove dirt 6 Fli...

Страница 35: ...of the unit Figure 79 Figure 78 Remove three 3 nuts securing ember bed in place 3 Remove injector orifice from left burner bracket with a 1 2 wrench 4 Install conversion orifice Refer to Table 3 5 The...

Страница 36: ...ough clearance holes into the bottom of the control panel 2 Thread and tighten 3 8 nuts back onto pem studs on underneath side of control panel reversing Step 1 shown in Figure 78 3 Reinstall logs as...

Страница 37: ...and burner must all be kept free of dust and unobstructed by debris Inspect these areas before each use and clean as necessary 1 Turn the burner OFF and let the heater cool completely before cleaning...

Страница 38: ...latches 6 00 Figure 82 Release the latches to release the glass frame NOTE Shown with out top for clarity Inspect the Vent System Annually Have the vent system inspected annually by a qualified techni...

Страница 39: ...iring diagram 12 99 Power Schematic Diagram NOTE IF ANY OF THE ORIGINAL WIRE AS SUPPLIED WITH THEAPPLIANCE MUST BE REPLACED IT MUST BE REPLACED WITH TYPE SF 2 200 C WIRE OR ITS EQUIVALENT Wiring Diagr...

Страница 40: ...cations prices and discontinue colors and products at any time without notice Service Parts List Ref Description Intrepid 1 Log Set Complete 20012552 1a Log Rear 20013111 1b Log Right 2012549 1c Log L...

Страница 41: ...0012218 24a Pilot Assembly 3Way N DV RN 0 199 706 Pilot Assembly 3Way N DV RP 0 199 703 10002264 10002265 24b Pilot PSE NA175 Pilot PSE LP175 10001115 20001116 25 Pilot Top Convertible 10002266 26 The...

Страница 42: ...t 30004239 30004237 30004238 30004240 30004241 30004242 30003182 Bordeaux 30006762 30006760 30006761 30006763 30006764 30006765 30006716 Brown Majolica 30004921 30004919 30004920 30004922 30004924 300...

Страница 43: ...n The fan helps distribute heated air from within the firebox out into the room The fan is controlled by a snapstat that turns power on and off as the firebox temperature rises above and falls below a...

Страница 44: ...after the sale of the product by an independent authorized HHT dealer distributor whichever occurs earlier However the warranty shall commence no later than 24 months following the date of product shi...

Страница 45: ...ior and exterior surface finishes may occur This is not a flaw and is not covered under warranty Damage to printed plated or enameled surfaces caused by fingerprints accidents misuse scratches melted...

Страница 46: ...ey or venting installation LIMITATIONS OF LIABILITY The owner s exclusive remedy and HHT s sole obligation under this warranty under any other warranty express or implied or in contract tort or otherw...

Страница 47: ......

Страница 48: ...ntcasting com Based on CSA P 4 1 09 Based on CSA P 4 1 09 Recherchez dans la brochure les caract ristique de rendement nerg tique de foyer au gaz nerguide Selon CSA P 4 1 09 Efficiency Ratings Model E...

Отзывы: