background image

11

8390-975

Vermont Castings • Defiant® Model 1975-CAT-C Installation Manual_R8  •  02/21

U.S.

Canada

A

44"

48" (1219 mm)

B

46"

50" (1270 mm)

C

12"

10"

12" (305 mm) 8" Connector

10" (250 mm) 6" Connector

D

6"

8" (203 mm)

E

6"

8" (203 mm)

F

16"

18" (460 mm)

F. Floor Protection

A tremendous amount of heat radiates from the bottom plate 

of your stove. The floor area directly under and around the 

stove will require protection from radiant heat as well as from 

stray sparks or embers that may escape the firebox.
Heat protection is provided with the use of the Bottom Heat 

Shield supplied with the stove. 
Most installations will require the bottom heat shield to be 

attached. Only when the stove is placed on a completely 

noncombustible surface such as unpainted concrete over 

earth may it be used without the heat shield. 
With the bottom heat shield installed this appliance was 

tested with spark and ember protection only. There is no 

required "R" value, and the floor protector only needs to be 

a non-combustible material, e.g. ceramic tile or sheet metal.

Important: All installations on a combustible floor require 

the use of the supplied bottom heat shield.

The Defiant does not require R value floor protection.
The minimum floor protector material is 20 gauge sheet metal. 

Other floor protector materials that can be used include Type 

I hearth pads, ceramic tile, stone, brick, etc.

Protection requirements vary somewhat between the Untied 

States and Canada as follows:

In U. S. installations

 the floor protector is required under the 

stove and must extend at least 16" (not including the ash lip) 

from the front of the stove (“F,” Figure 2.10), and at least 6" 

from the sides and rear. (“D” and “E,” Figure 2.10)
In  rear  venting  configurations,  floor  protection  must  also 

extend under the chimney connector and 2" to either side. 

(“C,”  Figure  2.10)  For  the  8"  (203  mm)  connector,  the 

protector must be a minimum of 12" (305 mm) wide. For the 

6" (152 mm) connector, the protector must be 10" (254 mm) 

wide. The protector must be centered under the connector.

To meet these requirements, a floor protector must be at least 

39" wide and 45" deep.

In Canada:

 A  noncombustible  floor  protector  is  required 

under the stove as well. The floor protector must extend 18" 

(457 mm) to the front (“F,” Figure 2.10), and 8" (203 mm) from 

the sides and rear. (“D” and “E,” Figure 2.10)
To meet these requirements, a floor protector must be at least 

43" (1092 mm) wide and 49" (1245 mm) deep.

Figure 2.10

 - Required floor protection dimensions.

D

E

A

B

A

E

C

ST500

Defiant

floor protection

1/31/02  djt

E

F

E

F

Содержание Defiant 1975T-CAT-C

Страница 1: ...nd use of this wood burning room heater Failure to follow these instructions could result in property damage bodily injury or even death Do not store or use gasoline or other flammable vapors and liqu...

Страница 2: ...ot be obstructed Damper must be open before opening doors Do not overfire Glowing parts indicate overfiring The space heater must be installed with the legs provided attached as shown in the installat...

Страница 3: ...Fan Kit Installation 21 J Installing Removing Catalyst 21 4 Smoke Alarm Safety Tips A Smoke and CO Detectors 22 B Safety Tips 22 5 Operation A Air Controls 23 B Damper Adjustment 23 C Conditioning Yo...

Страница 4: ...birth defects or other reproductive harm For more information go to www P65Warnings ca gov Proposition 65 Warning Fuels used in gas woodburning or oil fired appliances and the products of combustion o...

Страница 5: ...nsions Figure 1 1 Drawing Not to Scale 32 3 8 822mm 28 7 8 733mm 31 1 2 800mm 5 1 8 130mm 19 483mm 1693 Defiant dimensions 1 02 29 7 8 759mm 23 5 8 600mm 19 483mm 26 660mm C L 28 7 8 733mm Rear Ventin...

Страница 6: ...ure to follow these installation instructionsmayresultinadangeroussituation including a chimney or house fire Follow all instructions exactly and do not allow makeshift compromises to endanger propert...

Страница 7: ...x 203 mm and into a round flue with nominal flue of 6 152 mm Whatever the flue collar size this appliance may be vented into larger chimneys as well However chimneys with liners larger than 8 x 12 203...

Страница 8: ...NOTE Special slip pipes and thimble sleeves that form telescoping joints between sections of chimney connector are available to simplify installations They often eliminate the need to cut individual...

Страница 9: ...ch until it is flush with the inner flue wall Do not extend it into the actual flue passage as this could interfere with the draft The thimble sleeve should protrude 1 2 25 50 mm into the room Use fur...

Страница 10: ...le wall high temperature chimney with an inside diameter the same as the chimney connector at least one inch of solid insulation and a minimum of 9 229 mm air space between the outer wall of the chimn...

Страница 11: ...t require R value floor protection The minimum floor protector material is 20 gauge sheet metal Other floor protector materials that can be used include Type I hearth pads ceramic tile stone brick etc...

Страница 12: ...iance is installed in a corner and no shield is used the corners of the stove top must be at least 5 127 mm from nearby walls Clearances may be reduced only by means approved by the regulatory authori...

Страница 13: ...or less from the face of a fireplace must have a minimum clearance of 22 554 mm measured from the stove s top side edge If the trim extends more than 3 4 19 mm it is subject to the requirements for w...

Страница 14: ...Clearances Unprotected NFPA 211 Protected A Mantel Trim 41 1041 mm 29 737 mm B Top Trim 28 711 mm 21 533 mm C Side Trim 14 356 mm 14 356 mm D Side Wall 21 533 mm 11 280mm Figure 2 13 Maintain clearanc...

Страница 15: ...ing is required for all installations of the Defiant Stove Clearance Unprotected Surface No Connector Heat Shield Protected Surfaces1 with Connector Heat Shield Stove Installed Parallel to Wall Stove...

Страница 16: ...Stove Installed Parallel to Wall Stove Installed Parallel to Wall For use with either 6 or 8 flue collar chimney connector E F D D D ST855a Defiant 2n1 Clearance Diagrams D A B L M O O K H K I P N A...

Страница 17: ...for installations with either 6 or 8 flue collars Double Wall Connector Side A Rear B Corner C Side D Rear E Corner F 36 1 2 927 mm 21 533 mm 16 406 mm 20 1 2 521 mm 9 229 mm 16 406 mm ST511 Defiant...

Страница 18: ...allation vertical chimney connector two wall shields Reduced clearances for both rear and side walls Wall shields may meet at corner if desired Shielding for connector is centered behind connector Fig...

Страница 19: ...o the four hex bolts previously installed into base Figure 3 4 The outside air cutout hole should be toward the rear of the stove 3 Attach the heat shield sides by passing the slots over the bolt head...

Страница 20: ...he primary air thermostat handle is the smaller of the two black handles Secure the handle to the stub on the right side of the stove with an 8 32 x 2 slot head machine screw Figure 3 7 WARNING The fl...

Страница 21: ...rear edge of the heat shield 6 Fan will not operate until stove reaches approximately 109 F 7 Plug blower cord into a grounded outlet Do not remove ground prong from plug Route power cord to avoid hea...

Страница 22: ...If you install a detector in the same room locate it as far away from the stove as possible B Safety Tips Conveniently locate a Class A fire extinguisher to contend with small fires Be sure the fire...

Страница 23: ...it can be further burned before passing up the chimney Figure 5 3 The damper should always be either fully open or fully closed There are no intermediate positions When closing the damper be sure to p...

Страница 24: ...temperature One method of reducing emissions during a cold start up is the use of a top down kindling procedure In this place larger pieces of kindling on the bottom of the kindling pile followed by s...

Страница 25: ...wood with below 14 moisture content This may result in continuous very high temperatures in the secondary combustion area and damage the combustor Never kindle a fire with colored paper or paper that...

Страница 26: ...a safe distance from the heater and keep it out of the areas around the heater used for refueling and ash removal Surface Thermometer is a Valuable Guide to Operation An optional surface thermometer...

Страница 27: ...be moved from right to left F Ash Disposal IMPORTANT Check the level of ash in the ash pan before reloading the stove If the ash level is close to the top edge of the pan empty the pan according to th...

Страница 28: ...se fire Empty the ash pan regularly typically every one to three days The frequency will vary depending on how you operate your appliance ash will accumulate faster at higher heat outputs Removed ash...

Страница 29: ...common wisdom tells us that a taller flue draws better than a short one This isn t necessarily so If a chimney is tall enough to meet the safety requirements of the 2 3 10 foot rule then adding more h...

Страница 30: ...d performance and year of reliable heating Single Venting Each airtight stove requires its own flue If an airtight stove is vented to a flue that also serves an open fireplace or a leakier stove it s...

Страница 31: ...accumulates on the glass surface should be removed regularly to prevent etching To clean the glass follow this procedure Be sure the glass is completely cool Clean the glass with water or a cleaner ma...

Страница 32: ...se securely to prevent accidental opening and should close tightly to prevent air from leaking into the fire chamber The door handle will be positioned vertically when the door is closed Over a period...

Страница 33: ...s unless the involved parts are disassembled and then put back together If this is the case the job should be done only by a qualified service technician 5 16 diameter gasket seals the following parts...

Страница 34: ...ct or clean the chimney yourself contact your local Vermont Castings dealer or a professional chimney sweep Maintenance Schedule The Stove Daily Clear any ash build up from around the air holes and co...

Страница 35: ...ity of your fuel In warm weather draft is weaker than it is in colder winter weather and fires can burn sluggishly Small hot fires are a good solution under these conditions Burning green insufficient...

Страница 36: ...by fly ash deposits on the catalytic element However continue the inspections of the chimney system for a few weeks to ensure that proper performance continues If you continue to find a significant cr...

Страница 37: ...ica Brown 1979 CAT C Bordeaux 1980 CAT C Twilight 1975T CAT C Classic Black w Transition Doors 9 80 21 20 17 19 16 18 10 11 2 13a 14 15 13b 63 58 32 59 3 36 29 81 39 40 47 38 12 45 37 31 50 51 52 55 7...

Страница 38: ...e Quadrant Left 30002399A 11 Griddle Quadrant Right 30002401A 12 Griddle 30005257A 13 Complete Griddle Handle Assembly 30002775 Y 13a Griddle Handle Wood 1600661 Y 13b Griddle Handle CRS BN1 30002715...

Страница 39: ...r Set SRV30002810 Bolt 5 16 18 x 1 Pkg of 12 27887 12 Nut 5 16 18 x Pkg of 12 SRV8787 007 12 38 Door Handle Bracket 30002844 39 Bottom 30005240A 40 Ashlip Classic Black 30002811A Biscuit SRV30002870 B...

Страница 40: ...asket 1 00 30002422 61a Left Door Shell Enamel Parts Classic Black 30002813A Biscuit SRV30002876 Bordeaux SRV30006703 Majolica Brown SRV30004842 Twilight SRV30007132 Left Door Sub Assembly Shell Ename...

Страница 41: ...olica Brown 30004839 Twilight 30007134 67b Right Door Transition Door Enamel Classic Black 30007090A Biscuit SRV30007092 Bordeaux SRV30007096 Majolica Brown SRV30007094 Twilight SRV30007108 Right Door...

Страница 42: ...83b Bottom Heat Shield Left Wing 30005039 84 Grate Bottom 30005234A 85 Thermostat Assembly 5005470 Y 86 Thermostat Cable 5005471 Y 87 Thermostat Friction Spring Pkg of 10 1201846 10 88 Primary Air Va...

Страница 43: ...er or distributor whichever occurs earlier However the Warranty coverage shall commence no later than 24 months following the date of Product shipment from HHT regardless of the installation or occupa...

Страница 44: ...g devices such as exhaust fans or forced air furnaces or other such causes 6 use of fuels other than those specified in the operation instructions 7 installation or use of components not supplied with...

Страница 45: ...45 8390 975 Vermont Castings Defiant Model 1975 CAT C Installation Manual_R8 02 21...

Страница 46: ...46 8390 975 Vermont Castings Defiant Model 1975 CAT C Installation Manual_R8 02 21 352 Mountain House Road Halifax Pa 17032 www vermontcastings com...

Отзывы: