BFC36 Balance Flue Heat-Circulating Fireplace

7412647

Offset Installation

In order to clear an obstruction, it may be necessary to 
offset chimney from vertical. This is accomplished by 
using elbows. Use the 

30° Offset Elbow

 table on Page 

5 to determine proper offset and parts required.
Each offset requires two (2) elbows.  The second elbow 
is equipped with support straps.  It is very important to 
install the second elbow in each offset as close to the 
ceiling or support as possible so that the elbow straps 
can be secured to framing members to help support the 
weight of the chimney.
Determine offset distance of your chimney arrangement 
from centerline of fireplace to centerline of chimney 
where it is to pass through ceiling.
Locate center point of the chimney on ceiling as though 
a straight up chimney arrangement is to be used.  Mea-
sure your offset dimension from straight up chimney 
center point on ceiling.

Ceiling Chimney Hole/ 

Possible Obstructions

The size of the hole in ceiling will vary with the angle at 
which the chimney passes through ceiling. 
Drive a nail up through ceiling at marked chimney cen-
ter point. Go to floor above and see where hole will be 
cut. Check to see where existing ceiling joists and other 
possible obstructions are located...i.e. wiring, plumbing 
etc... If necessary, re-position chimney and/or fireplace 
to avoid obstructions.

Cutting the Hole

Cover fireplace collar opening and cut proper sized 
chimney hole in chimney.  

Framing the Ceiling Hole

Frame the ceiling chimney hole as shown in Figure 
10.  It is good practice to use framing lumber that is the 
same size as the ceiling joists; this is a requirement at 
attic level.

The 

inside dimension

 of the frame 

must be 

the same 

as the hole size selected from Figure 11 in order to 
provide required the 2” (51mm) air space between the 
outside diameter of the chimney and the edges of the 
framed ceiling hole.

FPC556a

BFC36

LOCATE CENTER LINE

Circulating model

8/21/00   djt

8

���

"

(222mm) 

Chimney Centerline

Actual Center-

point

Plumb Line

Plumb Bob

Imaginary Center-

point

FPC556a

Fig. 9

  Locate centerline of chimney with plumb line.

The following table gives firestop spacer model num-
bers:

Chimney Hole Size

 

 

 Angle of Chimney    

 

 

  at Ceiling 

  Size of Chimney 

Vertical 

 

30°

 

 

FS2A 

 

FS6A

 

8” Flue 

17

¹⁄₂

” x 17

¹⁄₂

”  

17

⁷⁄₈

” x 29

⁵⁄₈

 

 

(445 x 445mm)  (454 x 753mm)

New 

Framing 

Members

Existing 

Ceiling 

Joists

Fig. 10 

 Typical frame for ceiling chimney hole.

FP551b

17 1/2"

Framing chimney hole

5/13/99   djt

Ceiling

Chimney 

Hole

17

¹⁄₂

(445mm)

17

¹⁄₂

(445mm)

FP551b

Fig. 11

  Ceiling chimney hole sizes necessary for installing 

firestop spacer.

Содержание 647 BFC

Страница 1: ...he U S Canada Underwriter s Laboratories Report No MH6018 DO NOT DISCARD THIS MANUAL Retain for future use 7412647 8 05 Rev 10 410 Admiral Blvd Mississauga Ontario Canada L5T 2N6 905 670 7777 www majesticproducts com www vermontcastings com CFM Specialty Home Products Homeowner s Installation and Operating Manual ...

Страница 2: ... with a CFM Specialty Home Prod ucts fireplace system notwithstanding any independent testing laboratory or other third party approval of such component parts or accessory Any such action may possibly cause a fire hazard Consult local building codes to ensure that you are in compliance before installing the fireplace This fireplace and chimney system must be vented to the out of doors Do not obstruct ...

Страница 3: ...nge 647 BFC36 specs 8 18 00 djt 13 Dia 343mm Rough Opening Width 43 Rough Opening Height Rough Opening Depth Gas Line Access 51 1297mm 51 1297mm 1 8 3 4 m m 197mm 23 584mm 610mm 624mm 39 997mm 246mm 35 889mm 279mm Gas Line Access 902mm 36 914mm 1092mm 11 Dia 179mm 8 Dia 203mm 9 1 8 m m A B C FP1531 hearth dimensions 9 04 djt Front Width Back Width Depth A B C BFC36 32 20 17 826 mm 519 mm 451 mm FP...

Страница 4: ...ftstop Standoff Surround Trim Ledge Standoff Glass Door Romex Pigtail Gas Line Access Knock out Each Side Air Inlet Basket Grate Bottom Grille Metal Safety Strip s Shown not inplace 1 2 or 3 pieces Nailing Flange Top Grille and Air Outlet Gas Line Ac cess Hole Each Side Ceiling Level Firestop Batt Insulation Cut out around firestop FP554c Fig 2 Fireplace and chase parts identification ...

Страница 5: ...et of angled run of chimney Chimney supports are required for every 30 feet and 60 feet of vertical chimney height above the hearth Determine the offset distance of your chimney arrangement from the centerline of the fireplace to the centerline of the chimney where it is to pass through the first ceiling NOTE This offset distance may not be your full offset distance See Examples 2 and 3 Fig 3 Chimne...

Страница 6: ...45 elbows in Canada per fireplace may be used 6 A guy wire stabilizer is required for chimneys extend ing more than 6 1 8m above a roof line The Ten Foot Rule Major U S building codes specify a minimum chimney height above the roof top The Ten Foot Rule is a fire safety rule and not a draft rule To ensure proper draft it is recommended that you always meet or exceed the Ten Foot Rule especially when...

Страница 7: ...the chimney system should be run contact your Ver mont Castings Majestic Products dealer for assistance Installation Insulating Fireplace Enclosure for Cold Climates If you live in a cold climate it is not required but highly recommended that you insulate fireplace enclosure to eliminate cold air penetration as much as possible Insulate base of fireplace with a noncombustible insulation rated for a ...

Страница 8: ... nuts must be tight NOTE Check local building codes to determine if junction box is required at the romex pigtail house wire connection Also check junction box and speed control SCVS installation instructions The Model FKSX A blower assembly is preinstalled in the BFC36 FP1062 romex pigtail 8 21 00 djt Romex Pigtail Provided Fireplace Electrical Coverplate Wire Nuts Not pro vided Ground Black Whit...

Страница 9: ...ut Check to see where existing ceiling joists and other possible obstructions are located i e wiring plumbing etc If necessary re position chimney and or fireplace to avoid obstructions Cutting the Hole Cover fireplace collar opening and cut proper sized chimney hole in chimney Framing the Ceiling Hole Frame the ceiling chimney hole as shown in Figure 10 It is good practice to use framing lumber tha...

Страница 10: ...in front of the fireplace This Z shaped safety strip is not provided but must be fabricated of metal with each horizontal leg at least 1 38mm wide and equal in length to the metals strips provided with the fireplace NOTE Safety strips are not required over non com bustible floors where all supports at the base of the fireplace are noncombustible Four 4 nailing flanges are supplied with the fireplace fou...

Страница 11: ...minimum required air space to chimney pipe for ceiling thickness up to 8 203mm When combined thickness of ceiling material ceiling joists and flooring material exceeds 8 203mm adjustments must be made in framing to assure that minimum air spaces to chimney are maintained Proper Firestop Spacer Installation Figure 16 shows different installation procedures for both an area that is an attic and an ar...

Страница 12: ...bustible insulation and roof structures WARNING Do not pack required air spaces with insulation or other materials Mark an outline of the roof hole around the center of the point nail NOTE Hole dimensions given in the chim ney top installation instructions are horizontal dimen sions therefore the hole size must be marked on the roof accordingly Cover the opening of the installed chimney so debris ...

Страница 13: ...ocal building codes to determine specific requirements for your city or state NOTE Other building materials may be required in addition to firestop spacers Finishing CAUTION All joints between the finished wall and the fireplace surround top sides must be sealed with non combustible material to prevent cold air leakage into the room Only noncombustible material may be applied to the facing of the firep...

Страница 14: ...ntel clearances 12 from top of grille opening 6 from top of grille opening Face Plate FP531b mantel clearances 9 03 djt 12 305mm Max 12 305mm Min 1 38mm 6 159mm Min Fig 19 Mantel clearance Combustible Mantel Shelf and Trim Finished Wall Stud Standoff Circulating Front Noncombustible Material Fireplace Opening 2 x 4 Stud Finished Wall Must be sealed with noncom bustible material Fireplace Front Sid...

Страница 15: ...al to protect hearth extension material Fig 21 Secure the hearth extension to the floor to prevent shifting using trim molding or other similar means at three 3 outer edges Seal crack between the fireplace hearth and hearth extension with a non combustible material Figs 21 and 23 Minimum Wall Clearances WITH Noncombustible Surround Facing WITHOUT Noncombustible Surround Facing Minimum Hearth Extensi...

Страница 16: ...ng Hearth Extension Equivalents To determine the thickness required for any new mate rial NEW K of new material per inch thickness required X of listed thickness K of listed material per inch material Example for Common Brick T new 5 0 0 458 x 0 50 in 5 46 in new required thickness FP550 BR BC SEALING DETAILS 9 29 97 Wall Covering Noncombustible Decorative Fac ing Seal all cracks between fireplace ...

Страница 17: ...seal between the pipe and tube Note Gas pipe should not come in contact with any wood structures until it has reached a point at least 1 25mm away from fireplace side BTU input of a gas appliance installed in fireplace should be rated less than 100 000 BTU Hr Gas pipe installation is intended for connection to a decorative gas appliance only when 1 incorporating an automatic shutoff device and 2 com...

Страница 18: ...0008275 5 Right Door Assembly Complete 20008276 6 Rear Firebrick 2353145 7 Side Firebrick two per fireplace 2353146 8 Hearth Firebrick 2353140 9 Nailing Flange four per fireplace 2422198 10 Fiberglas Rope Gasket Outer Collar 7547137 11 Top Refractory 2353147 12 Front Brick Retainer 2353163 13 Cable Clip For Blower Assembly 7522241 14 Plug Button two per fireplace 7522239 15 Door Gasket 20009567 16 Ce...

Страница 19: ...6 Balance Flue Heat Circulating Fireplace 7412647 BFC Balanced Flue Fireplace continued 25 Stud 3 8 16 x 1 20009776 26 Nut Hex Jam 3 8 16 Toplk 1203290 27 Black Fall Away Handle 20006382 Ref Description BFC36 ...

Страница 20: ...per ated only with CFM Specialty Home Products approved components If you use an unapproved component to make any modifications you may create a possible fire hazard and will void the CFM Specialty Home Products warranty In addition such action may void the coverage provided by the owner s insurance Accessories Hearth Extension Insulation Provides hearth extension floor protection EH2416 Grate for BR...

Страница 21: ...ing is not included TT200C Adapter Kit TT8CB is required Chase Top Housing Used with chase terminations to prevent rain entry FL88 8 flue Contemporary Flashing 8 6 12 with 8 flue Required for Contemporary Round Top 0 to 6 12 pitch termination to prevent rain entry 8 12 12 with 8 flue 6 12 to 12 12 pitch Chimney Sections 8 flue 81 1 long Used to build chimney systems 818 1 long 83 3 long 84 4 long Chim...

Страница 22: ...22 BFC36 Balance Flue Heat Circulating Fireplace 7412647 ...

Страница 23: ... is subject to the following conditions and limitations 1 This warranty is extended only to a Fireplace installed in the con tinental United States the state of Alaska and Canada only if and so long as the Fireplace is installed according to the installation instruc tions furnished with the Fireplace and operated at all times under nor mal conditions use and service according to the operative inst...

Страница 24: ...410 Admiral Blvd Mississauga Ontario Canada L5T 2N6 905 670 7777 www majesticproducts com www vermontcastings com CFM Specialty Home Products ...

Отзывы: