VENTING INSTALLATION
•
The maximum number of 90° elbows per side wall
installation is three (3).
Figure 20
•
If a 90° elbow is fitted directly on top of the fireplace
flange, the maximum horizontal vent run before the ter
-
mination or a vertical rise is 36" (914 mm).
Figure 21
A: 10’
B: 7’
7’6”
FP1959
max run w/elbows
Figure 22 -
Maximum Vent Run with Elbows
Horizontal 90° Elbow = 3' Reduction
FP1959
A + B = 17' Maximum
FP1176
max 90 bends
Figure 20 -
Maximum Three (3) 90° Elbows
Per Installation
3 x 90°
Elbows
3 x 90°
Elbows
FP1176
Figure 21 -
Maximum Horizontal Run with No Rise
FP1177
• If a 90° elbow is used in the horizontal vent run (level
height maintained) the horizontal vent length is reduced
by 36" (914 mm)
Figure 22.
This does not apply if the
90° elbows are used to increase or redirect a vertical
rise.
Figure 23
Example:
According to the vent graph (
Page 15
) the
maximum horizontal vent length in a system with a 7.5'
vertical rise is 20’ (6 m) and if a 90° elbow is required in the
horizontal vent it must be reduced to 17' (5.2 m).
In Figures 22 and 23,
Dimension A plus B must not be
greater than 17' (5.2 m).
Figure 23 -
Horizontal Run Reduction
A
B
7’6”
90°
FP2413
horz run reduct
FP2413
When installing the appliance as a rear vent unit, the 90°, 45° transition elbow attached directly to the rear of the unit
is NOT INCLUDED in the following criteria and calculations, and unless specifically mentioned should be ignored
when calculating venting layouts.