Installation
Wiring
Note
Verkada Inc. 405 E 4th Ave, San Mateo, CA 94401
All specifications are subject to change without notice
Copyright © Verkada Inc. All rights reserved.
Current Limiting Resistor
If a powered peripheral has inrush current over 10A, an in-line current limiting power
resistor of 10
Ω
should be used to ensure peripheral does not exceed max power draw,
which may disrupt normal operation.
Max Line Resistance
The maximum line resistance for input wire runs should be less than 100
Ω
, exclusive of
end-of-line supervision resistors.
Max Power
For programmable 12V Outputs A and B: 1A max per output. For 12V AUX terminals 2A max
combined.
End-of-Line Resistor (EOLR) Supervision
EOLR supervision of inputs is optional on the BP41, and resistors do not need to be
installed for normal operation. The panel does support single EOLR and double EOLR
supervision modes. The supervision mode for each input can be configured in
Command. 1K
Ω
resistors may be used for both single and double EOL supervision.
Battery Backup
Battery should be sized to provide at least 4 hours of operation. The BP41 consumes
350mA with no sensors connected.
AC Field Wiring
If AC power is brought in via conduit, cut and splice wire going from AC inlet to PSU.
6