background image

ZL0030-0C 

PAGE 3 

©2012 Veris Industries   USA 800.354.8556 or +1.503.598.4564  / [email protected]  

02121

Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of  Veris Industries, L.L.C. in the USA and/or other countries.

TM

MSC SERIES

INSTALLATION GUIDE

SENSOR ADJUSTMENT SETTINGS

The adjustment panel is located on the front of the sensor housing. Gently pry off the 
cover with a small flathead screwdriver.

PIR and Ultrasonic

1

4

3

2

Photocell Dial

Mode Switch

DIP Switches

Sensitivity Dial

Dual Technology

1

4

3

2

Photocell Dial

Mode Switch

DIP Switches

Sensitivity Dial

Mode Switch:  

Determines when lights are turned on or remain on.

Sensor

Mode

Description

PIR and 

Ultrasonic

A

Automatic mode. Normal, default setting. Lights turn on or 

remain on only when the sensor detects motion.

M

Manual override ON mode. Lights are always on.

Dual Technology

1

Instant ON setting. Either PIR or ultrasonic detection turns 

the lights on or causes the lights to remain on.

2

Normal, default setting. Only PIR detection turns the lights 

on. Either PIR or ultrasonic detection causes the lights to 

remain on.

3

Override ON setting. Lights are always on.

Sensitivity Dial:  

Determines the amount of movement required to trigger the 

sensor and the distance from which movement is detected. Turn the dial to the 
desired setting (MSCP1000:  60% to 100% of max.; MSCU2000, MSCD2000:  10% to 
100% of max.). The default sensitivity setting is 100%.

Note:  Consider the characteristics of the room when adjusting the sensitivity of 
the Ultrasonic and Dual Technology sensors. Hard surfaces (concrete, tile, glass) 
are reflective and create a higher sensitivity for ultrasonic detection. Soft surfaces 
(carpet, drapes, acoustical tile) absorb some of the ultrasonic energy and reduce the 
unit’s sensitivity. Building additions, such as cubicles and walls, may also require a 
higher sensitivity setting.

Photocell Dial:  

Sets the level above which ambient light will not trigger the sensor. 

Set the ambient light level from 0.5 to 250 foot-candles. Turn the dial to the desired 
setting (minimum setting is fully countercockwise; maximum is fully clockwise). The 
default photocell setting is 250 foot-candles. This setting also disables the photocell 
(i.e., ambient light will not inhibit sensor operation).

Time Delay Switches:  

A set of four DIP switches determines how long lights will 

stay on after motion is no longer detected. Settings range from 15 seconds to 30 
minutes. The default time delay setting is 18 minutes. Possible DIP switch settings 
are shown in the table below.

DIP Switch Number

Time Delay

1

2

3

4

15 sec. (test setting)

2 min.

4 min.

6 min.

8 min.

10 min.

12 min.

14 min.

16 min.

18 min. (default setting)

20 min.

22 min.

24 min.

26 min.

28 min.

30 min.

—  =  Off

  

  =  On

To reduce unwanted detection, such as people moving in adjacent areas, partially 
mask the lens of the PIR or Dual sensor with the supplied white masking strips.

Masking Strip

Sensor with Masking

Field of View from the Top

CONFIGURATION

1.  Turn on the circuit breaker and any wall switches that supply power to the sensor.

2.  When first installed, allow the sensor to warm up for a few minutes before it is 

fully operational. When the sensor detects motion, the LED on the housing flashes 
for approximately 0.5 seconds, and the lights turn on or remain on.

3.  Set the Time Delay to the test setting of 15 seconds. 

4.  Vacate the room until the lights turn off.

5.  Re-enter the room. Lights should turn on immediately. If not, verify correct sensor 

wiring.

6.  Adjust settings as desired.

Отзывы: