INSTALLATION GUIDE

 Z202366-0M 

page 6 

©2008 Veris Industries   USA 800.354.8556 or 503.598.4564  / [email protected]   

02081

configuration

1

1

2

4

8

16 32 64 128

O

N

1

1.  

Communications Configuration:

  Communications parameters for the H704 

series are field selectable for your convenience. Please see Product Diagram 
section for selector location. The following parameters are configurable:

Parity On or Off

• 

Parity: Odd or even

• 

Wiring: Two or four

• 

Baud Rate:  2400, 4800, 9600 or 19200

• 

The values of each dip switch are as follows:

1=1
2=2
3=4
4=8
5=16
6=32
7=64
8=128

To determine an address you simply add the values of any switch that is on. 

For example:

or

H704 series can be addressed as any whole number between and including 1-247. 

Each unit is equipped with a set of 8 dip switches for addressing. See below.

LSB

MSB

VALUE

Example: 2-wire 9600 Baud No Parity (Default Only)

=

=

1
X
X
X
X
X
X

2

On

Off

3

Off

On

Off

On

4

Off
Off

On
On

5

6

7
X
X
X
X
X
X

8
X
X
X
X
X
X

2400 Baud
4800 Baud

9600 Baud

19200 Baud

2 wire

4 wire

Wiring, Baud Rate, Parity

Wiring

None

Even
Odd

Off
Off
On

Off
On
Off

Parity

Baud Rate

DESIRED RESULT

Switch #

Baud Rate and Parity Switch Setttings

40

2.  

Address Configuration:

  Each Modbus device on a single network must have a 

unique address. The switch block must be set to assign a unique address before the 
device is connected to the Modbus RS485 network. If an address is selected which 
conflicts with another device, neither device will be able to communicate. 

Switch number 4 has an ON Value of 8 and switch number 6 has an ON Value of 32.  
(8+32 = 40)

See the Communications Setup section for a pictorial listing of the first 63 switch 
positions.

Shop for Veris products online at:

1.877.766.5412

www.

PowerMeterStore

.com

Содержание H704-42

Страница 1: ...switch selectable 2400 4800 9600 19200 Parity DIP switch selectable NONE ODD EVEN Communication Format 8 data bits 1 start bit 1 stop bit Termination 5 position depluggable connector TX TX SHIELD TX RX TX RX Defaults Warning Register 60 of current sensor max configurable Alarm Register 70 of current sensor max configurable Breaker Size Register 20 A Incaseofacurrentfaultabove60A 120fortheHversion ...

Страница 2: ...s network 2 OpticalCommunicationsIsolation Optical isolators are used to separate 120 VAC portions of the circuit from the RS485 network 3 AliveLED Flashes once per second to indicate correct operation If steadily lit or out indicates internal failure 4 50 PinRibbonCableConnectors DataAcquisitionBoard 18 inch 457 mm ribbon cables are provided standard for easy snap connection of current sensor str...

Страница 3: ...ution and the possibility of condensation or high humidity Consideration must be given to the enclosure the correct use of ventilation thermal properties of the equipment and the relationship with the environment This symbol indicates an electrical shock hazard exists Documentation must be consulted where this symbol is used on the product Installation 11 375 289 mm 1 12 28 mm 5 75 146 mm Data Acq...

Страница 4: ... board 4 Check that CT serial numbers and meter serial numbers match Meter and CT sold as set with accuracy calibrated as a set For208 230VACPowerConnectionversion orderH704 42E H704 42 IE 522 4 3 3 2 342 0 522 4 3 3 2 342 0 522 4 3 3 2 342 0 522 4 3 3 2 342 0 ATA CQUISITION OARD ODBUS 5P TO gS 2IBBON ABLE 4O ONTROLLER OR 0 0ANEL OARD 0ANEL OARD 6 4 2 12 10 8 18 16 14 24 22 20 30 28 26 36 34 32 42...

Страница 5: ...connected together in a daisy chain fashion and properly terminated C The Modbus cable should be shielded twisted pair wire such as Belden 1120A The cable must be voltage rated for the installation 2 Wire 4 Wire 1 Connect 2 wire or 4 wire Modbus RS485 daisy chain network wiring WARNING After wiring the Modbus cable remove all scraps of wire or foil shield from the electrical panel This could be DA...

Страница 6: ...th a set of 8 dip switches for addressing See below LSB MSB VALUE Example 2 wire9600BaudNoParity DefaultOnly 1 X X X X X X 2 On Off 3 Off On Off On 4 Off Off On On 5 6 7 X X X X X X 8 X X X X X X 2400 Baud 4800 Baud 9600Baud 19200 Baud 2wire 4 wire Wiring Baud Rate Parity Wiring None Even Odd Off Off On Off On Off Parity Baud Rate DESIRED RESULT Switch Baud Rate and Parity Switch Setttings 40 2 Ad...

Страница 7: ...upport veris com 02081 communications setup DO NOT USE ZERO 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 Shop for Veris products online at 1 877 766 5412 www PowerMeterStore com ...

Страница 8: ...8 series or equivalent 5 Reconnect 120V to Data Acquisition Board 6 Reconnect power to panel 7 Check Alive LED for proper function See Product Diagram section for location service ACCESSORIES CBL008 Cable Ribbon 18 in 457 mm BCM CBL016 Cable Ribbon 48 in 1219 mm BCM CBL017 Cable Ribbon 60 in 1524 mm BCM CBL018 Cable Ribbon 72 in 1829 mm BCM CBL019 Cable Ribbon 97 in 2464 mm BCM CBL020 Cable Ribbon...

Отзывы: