background image

Z202815-0Q 

Page 2 of 4 

©2021 Veris Industries   USA 800.354.8556 or +1.503.598.4564  / [email protected] 0621 

 

12345 SW Leveton Drive, Tualatin OR  97062 USA

Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of  Veris Industries, L.L.C. in the USA and/or other countries.

Other companies’ trademarks are hereby acknowledged to belong to their respective owners.

H681x-V Series Installation Guide

Specifications

INPUTS

Frequency Range

50/60 Hz

 Leads

6 ft (1.8 m) 

20 ft (6 m)

ACCURACY

Accuracy

±1% of reading from 10% to 100% of rated current, specified with the 

primary conductor(s) centered in the CT window

OUTPUTS

Output at Rated Current

1 V or 0.333 V

MECHANICAL

Insulation

600 Vac

ENVIRONMENTAL

Operating Temp Range

2400 A models only:  -15 to 50 °C (5 to 122 °F);  

All other models:  -15 to 60 °C (5 to 140 °F)

Storage Temp Range

-40 to 70 °C (-40 to 158 °F)

Humidity Range

0 to 95% non-condensing

Altitude of Operation

3 km max.

Mounting Location

Not suitable for wet locations. For indoor use only.

WARRANTY

Limited Warranty

5 years

COMPLIANCE INFORMATION

Agency Approvals

UL61010-1, IEC 61010-1, EN 61010-1

Installation Category 

Category III, Pollution Degree 2

INPUTS

Frequency Range

50/60 Hz

 Leads

16 AWG, 8 ft (2.4 m), 20 ft (6 m)

ACCURACY

Accuracy

These CTs meet or exceed accuracy requirements specified in IEC 61869-2, 

Table 201, Class 1.

OUTPUTS

Output at Rated Current

1 V or 0.333 V

MECHANICAL

Insulation

600 Vac

ENVIRONMENTAL

Operating Temp Range

-15 to 60 °C (5 to 140 °F)

Storage Temp Range

-40 to 70 °C (-40 to 158 °F)

Humidity Range

0 to 95% non-condensing

Altitude of Operation

2 km max.

Mounting Location

Not suitable for wet locations. For indoor use only.

WARRANTY

Limited Warranty

5 years

COMPLIANCE INFORMATION

Agency Approvals

UL2808

Installation Category 

Category III, Pollution Degree 2

Split-Core

UL2808

Содержание H681-V Series

Страница 1: ...où ils dépasseraient 75 de l espace de câblage d une section de l équipement Restrict installation of current transformer in an area where it would block ventilation openings Éviter l installation du transformateur de courant dans un emplacement où il bloquerait les ouvertures d aération Restrict installation of current transformer in area of breaker arc venting Éviter l installation du transforma...

Страница 2: ...o 60 C 5 to 140 F Storage Temp Range 40 to 70 C 40 to 158 F Humidity Range 0 to 95 non condensing Altitude of Operation 3 km max Mounting Location Not suitable for wet locations For indoor use only WARRANTY Limited Warranty 5 years COMPLIANCE INFORMATION Agency Approvals UL61010 1 IEC 61010 1 EN 61010 1 Installation Category Category III Pollution Degree 2 INPUTS Frequency Range 50 60 Hz Leads 16 ...

Страница 3: ...uct indicating source side H6810 Small UL2808 100 400Amp A 3 23 82 mm B 1 4 36 mm C 1 4 36 mm D 1 12 28 mm E 3 25 83 mm F 4 12 105 mm H6811 Medium UL2808 600 800Amp A 4 95 126 mm B 2 9 74 mm C 2 46 63 mm D 1 2 31 mm E 5 36 136 mm F 5 83 148 mm H6812 Large UL2808 1000 2400Amp A 4 91 125 mm B 5 73 146 mm C 2 47 63 mm D 1 16 30 mm E 8 12 206 mm F 4 91 125 mm B E F C D A A B E C F D A B E C F D Dimens...

Страница 4: ...ose the CT with a suitable cable tie Fixer la barre en I à la barre en U de sorte qu elle reste fermement en place Fermer leTC à l aide d un serre câble adapté Failure to follow these instructions may result in injury fire or equipment damage Le non respect de ces instructions peut entraîner un risque de blessure d incendie ou de détérioration de l équipement WARNING AVERTISSEMENT Note These split...

Отзывы: