installation

1.  Remove the cover by pressing the tab at the top of the sensor while pulling 

outward from the top of the cover.

5.  Mount the backplate onto the wall using the screws provided.

6.  Wire the backplate. 

correct

incorrect

4.  Position the sensor vertically on the wall, 4 1/2 feet above the floor.

Five screwholes available; use a 
minimum of two for secure mounting.

2.  Remove the backplate by unfastening the sensor from the bottom of the backplate 

and pivoting the sensor outward.

3.  Punch out openings in the backplate.

POWER SOURCE

15 to 30VDC or 24VAC

DIGITAL CONTROL

RH IN

Temp IN

RH setpoint IN

Temp setpoint IN

Thermistor/RTD IN

Thermistor/RTD IN

-

-

-

+

RH output

GND

Thermistor/RTD

Thermistor/RTD

Temp output

RH Setpoint output

Temp Setpoint output

7.  Install and configure the sensor.

WARNING: Output select must be 
correct before applying power.

RH

YES 

AMP

 

VOLT

 

NO

YES 

RUN CAL

NO

TEMP

Minus

Plus

Enter

+

RH

SENSOR

TEMP

SENSOR

RH

YES 

AMP

VOLT

NO

YES 

RUN

CA

L

NO

TEMP

Minus

Plus

Enter

+

RUN/CAL JUMPER:

CAL Mode - allows full access to all 
features.
RUN Mode - allows access to relay 
setpoints ONLY.

RH YES/NO JUMPER:

YES - allows user to change RH setpoint
NO - user can NOT change RH setpoint 

TEMP YES/NO JUMPER:

YES - allows user to change TEMP 
setpoint 
NO - user can NOT change TEMP setpoint 

8.  Install the cover and snap into place.

Содержание HT Series

Страница 1: ...sformersecondaryisconnectedtosignalcommon soanisolationtransformeror dedicatedpowersupplymayberequired Specifiedaccuracywith24VDCsuppliedpowerwithrisinghumidity ResetRateistimerequiredtorecoverto50 RHafterexposureto90 RHfor24hours RTD Thermistorsinwallpackagesarenotcompensatedforinternalheatingofproduct HT Series HT Series Dimensions NOTICE This product is not intended for life or safety applicati...

Страница 2: ...ening the sensor from the bottom of the backplate and pivoting the sensor outward 3 Punch out openings in the backplate POWER SOURCE 15 to 30VDC or 24VAC DIGITALCONTROL RHIN TempIN RHsetpointIN TempsetpointIN Thermistor RTDIN Thermistor RTDIN RH output GND Thermistor RTD Thermistor RTD Temp output RH Setpoint output Temp Setpoint output 7 Install and configure the sensor WARNING Outputselectmustbe...

Страница 3: ...0º F user discretion RH and TEMP can be field calibrated by moving RUN CAL jumper to CAL position 2 Relative humidity allows for calibration offset of 10 RH user discretion ht operation instructions Enter Displayscreen Scrolldown Select Scrollup NormalOperation TemperatureSelection Use the and buttons to scroll to the Thermostat mode HumiditySelection Use the and buttons to scroll to the Humidista...

Страница 4: ... press to select setpoint in C if Celsius units are selected CONFIG CAL MODE Enter by any keypress when Run Cal jumper is in CAL position 4 5 5 R H 6 8 5 º F NORMAL MODE press to change press to select press to change press to select press to change press to select press to change press to select setpoint in C if Celsius units are selected press to change press to select options are 50 95 F 10 35 ...

Отзывы: