INSTALLATION GUIDE

H720

OPERATION

The H720 is a current-sensitive transducer that monitors current (amperage) in 
the conductor passing through it. The H720 has a 4-20 mA analog output that 
corresponds to 0-20 A to 0-200 A flowing through the conductor (adjustable Span 
setting). The status output is suitable for connection to building controllers or 
other appropriate data acquisition equipment operating at up to 30 volts. The H720 
requires a 12-30 VDC power supply to generate its output.

TROUBLESHOOTING

Problem

Solution

No Reading at Controller

• Check Zero and Span settings.
• Check for control voltage at sensor (< 30 V)
• Check for amperage in monitored conductor (> 1 A)

4x

0.5A

DANGER: 5A CTs can present hazardous voltages. 

Install CTs in accordance with manufacturer's instructions. 

Terminate the CT secondary before applying current.

H68xx-5A CT

240A 

300A:

5A 

> 200 A (Sensor max.)

CAUTION 

RISK OF EQUIPMENT DAMAGE

•  Derate the product’s maximum current for the number of turns 

through the sensing window using the following formula.

Rated Max. Amps ÷ Number of Turns = Max. monitored Amps
e.g. :  100A ÷ 4 Turns = 25 Amps max. in monitored conductor

•  Failure to follow these instructions can result in overheating 

and permanent equipment damage.

ZERO AND SPAN SETTING

< 1 A (Sensor Min.)

SENSED AMPS

4mA

20mA

0A

20 to 200A* 

*Adjusted with Span Setting

SENSOR OUTPUT

WIRING OPTIONS

Option 1:

COM

COM

+

OUT

+

PWR

4-20 mA

IN

PWR OUT

(12-30 VDC)

Span Zero

Automation 

Panel

H720

Option 2:

COM

COM 4-20 mA 

IN

COM

+

OUT

+

PWR

+

Span Zero

External 

Power 

Supply

Automation 

Panel

H720

NOTES

For load currents greater than sensor maximum rating:

 

Use a 5 Amp (H68xx series) Current Transformer (CT) as shown. This technique can be 
combined with wrapping (see below) to add range for a low current load on a high 
current source.

For load currents less than sensor minimum rating:

 

Wrap the monitored conductor through the center window and around the sensor 
body to produce multiple turns. This increases the current measured by the 
transducer.

Program controller to account 
for the extra turns, e.g., if four 
turns pass through the sensor 
(as shown), then divide the 
normal controller reading by 4.