A:  Voltage Leads
B:  Fuses
C:  Pulse Output Connector
D:  STATUS LED
E:  Pulse Rate Switches
F:  External CTs

VOLTAGE LEADS 
Connect the leads to the three-phase source to be monitored.  Input range is 
208 to 480VAC.

MANDATORY FUSE PER NEC
Maximum current draw is 60 mA.  Fuses provided by factory are rated 1/2A, 
600 VAC, 200 KAIC.

PULSE OUTPUT CONNECTOR
Please refer to wiring diagram on page 4.

STATUS LED
The LED blinks green when the product is functioning normally. It will blink 
slowly, approximately one second on, then one second off.

If  the  LED  is  red  and  blinking  slowly,  it  may  indicate  incorrect  wiring  or  a 
power factor that is less than 0.5.  If the LED is red and blinking fast the CT's 
maximum current rating has been exceeded or the pulse rate switches are 
incorrectly set.

PULSE RATE SWITCHES
These switches set the pulse output rate. Please refer to Figure 4 for settings.

EXTERNAL CTs (3 phase versions only)
These external CTs are permanently attached and must not be disconnected or 
used with other power meters.

PRODUCT DIAGRAM

A

B

C

D

E

F

FIGURE 1

Color match CTs and voltage leads!   Example: Clamp the red label CT around 
the power conductor connected to the red voltage wire.