INSTALLATION GUIDE

H738

OPERATION

The H738 is a current-sensitive switching device that monitors current (amperage) in 
the conductor passing through it. A change in the conductor’s amperage that crosses 
the adjustable switch threshold plus the hysteresis value causes the resistance of 
the FET status output to change state, similar to the action of a mechanical switch. 
In this model, the setpoint is adjustable through the action of a twenty (20) turn 
potentiometer (see the CALIBRATION section). An integrated relay allows start/
stop control. The status output is suitable for connection to building controllers or 
other appropriate data acquisition equipment operating at up to 30 volts. The H738 
requires no external power supply to generate its output.

TROUBLESHOOTING

Problem

Solution

No Reading at Controller

• Check sensor calibration (see above)
• Check for control voltage at sensor (< 30 V)
• Check for amperage in monitored conductor (>1 A)

Setpoint screw has no 

stops

The setpoint screw has a slip-clutch at both ends of its travel to 

avoid damage. Twenty turns CCW will reset the sensor to be 

most sensitive. Repeat calibration above.

Both LEDs are lit

Setpoint screw is too far clockwise. See solution above.

CALIBRATION

A. To monitor under-current (belt loss, coupling shear, status)

A

OK!

!

1. Turn setpoint screw 
clockwise until Status OPEN 
LED turns ON.

2. Slowly turn the screw counter-clockwise until the Status CLOSED LED just 
turns ON.

3.Turn the screw an 
additional 1/4 turn 
counter-clockwise for 
operational margin.

B.  To monitor over-current (mechanical problems, seized impeller)

A

OK!

!

3. Turn the setpoint 
screw an additional 
1/4 turn clockwise for 
operational margin.

1. Turn setpoint screw 
counter-clockwise until Status 
CLOSED LED turns ON.

2. Slowly turn the setpoint screw clockwise until the Status OPEN LED just turns ON.

OK!

STATUS

OK!

STATUS

Setpoint

Status

Open

STOP

Setpoint

Status

Closed

STOP

1/4

Setpoint

+

Setpoint

Status

Closed

STOP

Setpoint

Status

Open

STOP

+

1/4

Setpoint

Before beginning calibration, establish normal load conditions.

OK!

A

OK!

Then choose either A or B below.

4x

0.5A

DANGER: 5A CTs can present hazardous voltages. 

Install CTs in accordance with manufacturer's instructions. 

Terminate the CT secondary before applying current.

H68xx-5A CT

240A 

300A:

5A 

> 135 A (Sensor max.)

CAUTION 

RISK OF EQUIPMENT DAMAGE

•  Derate the product’s maximum current for the number of turns 

through the sensing window using the following formula.

Rated Max. Amps ÷ Number of Turns = Max. monitored Amps
e.g. :  100A ÷ 4 Turns = 25 Amps max. in monitored conductor

•  Failure to follow these instructions can result in overheating 

and permanent equipment damage.

< 1 A (Sensor Min.)

NOTES

For load currents greater than sensor maximum rating:

 

Use a 5 Amp (H68xx series) Current Transformer (CT) as shown. This technique can be 
combined with wrapping (see below) to add range for a low current load on a high 
current source.

For load currents less than sensor minimum rating:

 

Wrap the monitored conductor through the center window and around the sensor 
body to produce multiple turns. This increases the current measured by the 
transducer.