H622-20 Installation Guide

TM

Installation

1.   Disconnect and lock out power.

2.   Install the mounting bracket to the back of the electrical enclosure, no closer than 1/2” (12 mm) to an uninsulated conductor.

3.   Place the conductor to be monitored in the sensing cavity of the current sensor. Ensure the latch is closed. See Notes section 

below for currents under 2 A or above 20 A.

4.   Wire the output connections between the H622-20 and the controller (0 to 5 Vdc).

5.   Reconnect power.

6.   Scale the controller software to match the output of the H622-20.

Notes

For load currents greater than sensor maximum rating:

Use a 5 Amp (H681x series) Current Transformer (CT) as shown.

H68xx-5A CT

>175 A (sensor max.)

240 A

300A:

5A

4 A

 

DANGER: 5A CTs can present hazardous voltages. 
Install CTs in accordance with manufacturer's instructions. 
Terminate the CT secondary before applying current.

NOTICE

RISK OF EQUIPMENT DAMAGE

•  Never exceed the current sensor rating.
•  Derate the product’s maximum current for the number of turns 

through the current sensor window using the following formula:

Rated Max. Amps ÷ Number of Turns = Max. 

monitored Amps

e.g. :  100A ÷ 4 Turns = 25 Amps max. in 

monitored conductor

Failure to follow these instructions can result in overheating 
and permanent equipment damage.